5.4.6
Representation of analog values for resistance-type sensors
Table 5-15
Analog value representation for resistance-type sensors from 48 Ω to 6 kΩ
System
Resistive transducer range
Dec.
Hex.
48 Ω
150 Ω
300 Ω
600 Ω
6 kΩ
118,515 % 32767
7FFF
56.89 Ω
177.77 Ω
355.54 Ω
711.09 Ω
7.11 kΩ
Overflow
117,593 % 32512
7F00
117,589 % 32511
7EFF
56.44 Ω
176.38 Ω
352.77 Ω
705.53 Ω
7.06 kΩ
Overshoot
range
27649
6C01
100,000 % 27648
6C00
48 Ω
150 Ω
300 Ω
600 Ω
6 kΩ
Nominal range
75 % 20736
5100
36 Ω
112.5 Ω
225 Ω
450 Ω
4.5 kΩ
0,003617 % 1
1
1.74 mΩ
5.43 mΩ
10.85 mΩ
21.70 mΩ
217.0 mΩ
0 % 0
0
0 Ω
0 Ω
0 Ω
0 Ω
0 Ω
(negative values are physically impossible)
Undershoot
range
Analog modules
5.4 Representation of analog values
S7-400 Automation System Module Data
176
Reference Manual, Ausgabe 11/2016, A5E00850736-08