Wiring
4.4 Module status after power is switched on
Counter module FM 450-1
Manual, 02/2014, A5E03648739-02
35
4.3
Wiring Front Connectors
Cables
There are a few rules you must observe when selecting the cables:
●
The cables for the digital inputs must be shielded.
●
The cables for the count signals must be shielded.
●
You must apply the shields to the count signal cables both on the pulse encoder and in
close proximity to the module, e.g. via the shield application element.
●
Cables A and /A, B and /B, N and /N of the incremental 5-V encoder must be twisted in
pairs.
The following figure shows details relating to the connection of incremental 5-V encoders.