![Siemens Simatic S7-300 Installation And Operating Manual Download Page 199](http://html.mh-extra.com/html/siemens/simatic-s7-300/simatic-s7-300_installation-and-operating-manual_374640199.webp)
Analog modules
9.2 SM 336; AI 6 x 13 Bit
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
199
Assignable parameters for application 2
Table 9- 6
Parameters for application 2 of SM 336; AI 6 x 13Bit
Parameters
Range of values in standard mode
Type
Effective range
"Inputs 1" tab
Enable diagnostic
interrupt
Yes/no
Static
Module
Interference frequency 50 Hz/60 Hz
Static
Module
Group diagnostics
Yes/no
Static
Channel
Wire-break check (only
for 4 to 20 mA)
Yes/no
Static
Channel
Measurement type
Deactivated
4DMU
2DMU
V
Static
Channel
Measuring range
4 to 20 mA
0 to 20 mA
0 to 10 V
static
channel
"Inputs 2" tab
Safety mode
No (standard mode)
static
module
Monitoring time
—
static
module
"Redundancy" tab*
Redundancy
2 modules
static
module
Redundant module
Selection of an existing additional
module of the same type
static
Redundant module
pair
* The two analog values returned in a redundant configuration operating in standard mode must be
evaluated in the default user program.
9.2.6
Application 3: Safety mode SIL2/Cat.3/PLd
Introduction
Below are the wiring schemes and the parameter assignment of SM 336; AI 6 x 13Bit for
●
Application 3: Safety Mode SIL2/Cat.3/PLd.
Diagnostic messages, possible causes of the problem and their corrective measures are
found in tables
Diagnostic messages of SM 336; AI 6 x 13Bit and Diagnostic messages and
associated corrective measures for SM 336; AI 6 x 13 Bit in chapter "Diagnostic Messages