Analog modules
9.2 SM 336; AI 6 x 13 Bit
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
195
Assignable parameters for application 1
Table 9- 5
Parameters for application 1 of SM 336; AI 6 x 13Bit
Parameters
Range of values in standard mode
Type
Effective range
"Inputs 1" tab
Enable diagnostic
interrupt
Activated/deactivated
Static
Module
Interference frequency 50 Hz/60 Hz
Static
Module
Group diagnostics
Activated/deactivated
Static
Channel
Wire-break check (only
for 4 to 20 mA)
Activated/deactivated
Static
Channel
Measurement type
Deactivated
4DMU
2DMU
V
Static
Channel
Measuring range
4 to 20 mA
0 to 20 mA
0 to 10 V
static
channel
"Inputs 2" tab
Safety mode
No (standard mode)
Static
Module
Monitoring time
—
Static
Module
"Redundancy" tab
Redundancy
none
Static
Module
9.2.5
Application 2: standard mode with high availability
Introduction
Below are the wiring schemes and the parameter assignment of SM 336; AI 6 x 13Bit for
●
Application 2: standard mode with high availability
Diagnostic messages, possible causes of the problem and their corrective measures are
found in tables
Diagnostic messages of SM 336; AI 6 x 13Bit and Diagnostic messages and
associated corrective measures for SM 336; AI 6 x 13Bit in chapter "Diagnostic Messages