Digital modules
8.6 SM 326; DO 10 x DC 24V/2A (6ES7326-2BF01-0AB0)
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
157
Faulty diagnostics in case of short-circuit
When the fail-safe digital output module SM 326; DO 10 x DC 24V/2A detects a short-circuit
to L+ at a channel, or a short-circuit between channels which carry different signals, it
generates a diagnostic interrupt to report and passivate the faulty channel, including all other
channels in the section which contain this channel. Any short-circuit of longer duration leads
to the total failure of the module.
See also
Parallel Connection of Two Outputs for Dark Period Suppression (Page 151)
8.6.7
Technical Data - SM 326; DO 10 x DC 24V/2A
Overview
Technical data
Dimensions and Weight
Dimensions W x H x D (mm)
80 x 125 x 120
Weight
Approx. 465 g
Module-Specific Specifications
Number of outputs
10
Assigned address area
In the I/O input area
6 bytes
In the I/O output area
8 bytes
Cable length
Unshielded
600 m, maximum
Shielded
1000 m, maximum
with SIL3/Cat.4/PLe
200 m, maximum
Front connectors
40-pin
Maximum achievable Safety Integrity Level in safety mode
According to IEC 61508
SIL 3
According to EN 954-1
Category 4
According to ISO 13849:2006
PLe
Fail-safe performance characteristics
SIL 2
SIL 3
low demand mode (average probability of failure on
demand)
< 1.00E-05
< 1.00E-05
high demand / continuous mode (probability of a
dangerous failure per hour)
< 1.00E-09
< 1.00E-09