Station status 1
Table 10-13
Structure of station status 1 (Byte 0)
Bit
Description
Remedy
0
1: DP slave cannot be addressed by DP master.
•
Is the correct DP address set on the DP
slave?
•
Is the bus connector in place?
•
Does the DP slave have power?
•
Correct configuration of the RS485
Repeater?
•
Perform a reset on the DP slave.
1
1: DP slave is not ready for data exchange.
•
Wait for the slave to complete startup.
2
1: Configuration data sent by DP master to the DP
slave is inconsistent with slave configuration.
•
Was the software set for the correct
station type or DP slave configuration?
3
1: Diagnostic interrupt, generated by CPU RUN to
STOP transition
0: Diagnostic interrupt, generated by CPU STOP to
RUN transition
•
You can read the diagnostic data.
4
1: Function not supported; e.g. changing the DP
address at software level
•
Check
configuration
data.
5
0: This bit is always "0".
•
-
6
1: DP slave type inconsistent with software
configuration.
•
Was the software set for the right station
type? (parameter assignment error)
7
1: DP slave was configured by a DP master other
than the master currently accessing the slave.
•
The bit is always 1 if, for example, you are
currently accessing the DP slave via PG or
a different DP master.
The configuring master's DP address is
located in the "Master PROFIBUS address"
diagnostics byte.
Station Status 2
Table 10-14
Structure of Station Status 2 (Byte 1)
Bit
Description
0
1: The DP slave requires new parameters and configuration.
1
1: A diagnostic message was received. The DP slave cannot resume operation until the error
has been cleared (static diagnostic message).
2
1: This bit is always "1" if a DP slave exists with this DP address.
3
1: The watchdog monitor is enabled on this DP slave.
4
1: DP slave has received control command "FREEZE".
5
1: DP slave has received control command "SYNC".
6
0: This bit is always "0".
7
1: DP slave is disabled, that is, it has been excluded from cyclic processing.
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...