Addressing
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
7-7
CPU 314 IFM
The following addresses are assigned to the integrated I/O of CPU 314 IFM:
Table 7-2
Integrated I/O of CPU 314 IFM
Inputs/Outputs
Addresses
Remarks
20 digital inputs
124.0 to 126.3
of those are 4 Inputs for
integrated functions:
126.0 to 126.3
Optional utilization of Inputs for
integrated functions:
•
Counting
•
Counting
A/B
•
Frequency
measurement
•
Positioning
•
Interrupt
input
Refer to the Manual
Integrated functions
16 digital outputs
124.0 to 125.7
–
4 analog inputs
128 to 135
–
1 analog output
128 to 129
–
CPU 312C
The following addresses are assigned to the integrated I/O of CPU 312C:
Table 7-3
Integrated I/O of CPU 312C
Inputs/Outputs
Default: addresses
Remarks
10 digital inputs
124.0 to 125.1
of those are 8 Inputs for
technological functions:
124.0 to 124.7
6 digital outputs
124.0 to 124.5
of those are 2 Inputs for
technological functions:
124.0 to 124.1
All digital inputs can be programmed
as interrupt input.
Optional technological functions:
•
Counting
•
Frequency
measurement
•
Pulse width modulation
Summary of Contents for Simatic S7-300
Page 10: ...Contents S7 300 Programmable Controller Hardware and Installation x A5E00105492 01 ...
Page 16: ...Preface S7 300 Programmable Controller Hardware and Installation 1 6 A5E00105492 01 ...
Page 22: ...Quick Guide S7 300 Programmable Controller Hardware and Installation 2 6 A5E00105492 01 ...
Page 28: ...Product overview S7 300 Programmable Controller Hardware and Installation 3 6 A5E00105492 01 ...
Page 74: ...Configuring S7 300 Programmable Controller Hardware and Installation 4 46 A5E00105492 01 ...
Page 102: ...Wiring S7 300 Programmable Controller Hardware and Installation 6 18 A5E00105492 01 ...
Page 148: ...Commissioning S7 300 Programmable Controller Hardware and Installation 8 36 A5E00105492 01 ...
Page 236: ...Glossary S7 300 Programmable Controller Hardware and Installation 12 16 A5E00105492 01 ...