553BTechnical specifications
A.10 Communication interfaces
S7-1200 Programmable controller
756
System Manual, 11/2011, A5E02486680-05
Table A- 163 Power supply
Technical data
CM 1241 RS232
Power loss (dissipation)
1.1 W
From +5 VDC
220 mA
Table A- 164 RS232 connector (male)
Pin
Description
Connector
(male)
Pin
Description
1 DCD
Data carrier detect: Input
6 DSR
Data set ready: Input
2 RxD
Received data from DCE: Input
7 RTS
Request to send: Output
3 TxD
Transmitted data to DCE: Output
8 CTS
Clear to send: Input
4 DTR
Data terminal ready: Output
9 RI
Ring indicator (not used)
5 GND
Logic ground
SHELL
Chassis ground
A.10.4.4
CM 1241 RS422/485 Specifications
CM 1241 RS422/485 Specifications
Table A- 165 General specifications
Technical data
CM 1241 RS422/485
Order number
6ES7 241-1CH31-0XB0
Dimensions
30 x 100 x 75 mm
Weight
155 grams
Table A- 166 Transmitter and receiver
Technical data
CM 1241 RS422/485
Type
RS422 or RS485, 9-pin sub D female connector
Common mode voltage range
-7 V to +12 V, 1 second, 3 VRMS continuous
Transmitter differential output voltage
2 V min. at R
L
= 100 Ω
1.5 V min. at R
L
= 54 Ω
Termination and bias
10K Ω to +5 V on B, PROFIBUS Pin 3
10K Ω to GND on A, PROFIBUS Pin 8
Internal bias options provided, or no internal bias. In all cases,
external termination is required (
see Chapter 12, Communcations
Protocols, page xxx)
Receiver input impedance
5.4K Ω min. including termination