105BCommunication processor
12.3 Point-to-Point (PtP) communication
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
549
Table 12- 33 Condition codes
STATUS (W#16#....)
Description
80F0
CM or CB is RS485 and no signals can be set
80F1
Signals cannot be set because of Hardware flow control
80F2
Cannot set DSR because module is DTE
80F3
Cannot set DTR because module is DCE
12.3.2
Configuring the communication ports
The communication interfaces can be configured by two methods:
●
Use the device configuration in STEP 7 to configure the port parameters (baud and
parity), the send parameters and the receive parameters. The device configuration
settings are stored in the CPU. These settings are applied after a power cycle and a RUN
to STOP transition.
●
Use the PORT_CFG (Page 534), SEND_CFG (Page 535) and RCV_CFG (Page 537)
instructions to set the parameters. The port settings set by the instructions are valid while
the CPU is in RUN mode. The port settings revert to the device configuration settings
after a STOP transition or power cycle.
After configuring the hardware devices (Page 109), you configure parameters for the
communication interfaces by selecting one of the CMs in your rack or the CB, if configured.
The "Properties" tab of the inspector window
displays the parameters of the selected CM or
CB. Select "Port configuration" to edit the
following parameters:
Baud rate
Parity
Number of stop bits
Flow control (RS232 only)
Wait time
Except for flow control, which only the CM 1241 RS232 supports, the port configuration
parameters are the same regardless of whether you are configuring an RS232 or an RS485
communication module or the RS485 communication board. The parameter values can
differ.