Technical Specifications
Address identifier for ET 200U
DP Siemens
DP Standard
4DI or 008
8DI or 016
Number of inputs
Galvanic isolation
in groups of
4
yes (optocoupler)
4
Input voltage L+
rated value
for “0” signal
for “1” signal
24 V DC
–33 to 8 V
13 to 72 V
Input current at “1” signal
typ. 4.5 to 7.5 mA
Inherent delay
from “0” to “1”
from “1” to “0”
typ. 3 ms (1.4 to 5 ms)
typ. 3 ms (1,4 to 5 ms)
Fault LED (red)
no input voltage L+
Connection of 2–wire BERO
proximity switches
residual current
possible
v
1.5 mA
Length of cable
unshielded
max. 100 m (330 ft.)
Rated isolation voltage
(+9 V to L+)
isolation group
tested with
60 V AC
2
B
1250 V AC
Rated isolation voltage
(+9 V to )
isolation group
tested with
12 V AC
1
B
500 V AC
Current consumption
from +9 V (CPU)
from L+
5 mA
max. 35 mA
Power loss of the module
typ. 2 W
Weight
approx. 200 g (7 oz.)