background image

 

 

 

Securely Connecting 
and Monitoring 
RTU3041C to 
TeleControl Server 
Basic

 

 

SIMATIC RTU3041C / TeleControl Server Basic V3.1 / 
SINEMA Remote Connect Server

 

 

https://support.industry.siemens.com/cs/ww/en/view/109739240

 

 

 

 

Siemens 
Industry 
Online 
Support 

Summary of Contents for SIMATIC RTU3041C

Page 1: ...g and Monitoring RTU3041C to TeleControl Server Basic SIMATIC RTU3041C TeleControl Server Basic V3 1 SINEMA Remote Connect Server https support industry siemens com cs ww en view 109739240 Siemens Industry Online Support ...

Page 2: ...ons Claims for damages arising from a breach of material contractual obligations shall however be limited to the foreseeable damage typical of the type of agreement unless liability arises from intent or gross negligence or is based on loss of life bodily injury or damage to health The foregoing provisions do not imply any change in the burden of proof to your detriment You shall indemnify Siemens...

Page 3: ... GPS functionality of the RTU3041C 35 Creating tags for programming in the RTU3041C 38 Creating a program in the SIMATIC RTU3041C 50 Programming email transmission 53 Configuring a VPN Connection 59 Configuring the connection to the TeleControl Server 61 2 2 3 Configuring the TeleControl Server Basic 65 2 2 4 Configuring OPC UA Clients UaExpert 70 2 2 5 Loading the Configuration File 76 2 3 Operat...

Page 4: ...uts and supports position determination and time synchronization via GPS Requirements An RTU30X1C monitors the level of a rain overflow basin and securely transmits the encrypted data to the central station To conserve power the RTU30X1C is in sleep mode much of the time switching to an update or communication mode in predetermined cycles If the level exceeds a critical value the RTU30X1C informs ...

Page 5: ...able timed intervals the RTU3041C switches from sleep mode to update mode to read the inputs and process the program The position determination and the time synchronization of the RTU3041C is done via GPS Via the mobile data network the RTU3041C connects to the SINEMA Remote Connect Server and establishes an OpenVPN connection Then the RTU3041C connects to the TeleControl Server Basic and regularl...

Page 6: ...ed range The RTU3041C is configured via the Web Based Management WBM of the RTU3041C The blocks are graphically displayed and programmed via the Web Based Management WBM of the RTU3041C The communication is secured with OpenVPN For this purpose the RTU3041C connects to the SINEMA Remote Connect Server and establishes a VPN tunnel Note To enable a secure VPN connection you must set up port sharing ...

Page 7: ...TU3041C OPC UA Client OPC UA GPS signal Cell Phone VPN tunnel TeleControl Basic SINEMA Remote Connect Server Implemented functions The following functions are implemented in the application example Receiving a wake up SMS to wake up the RTU3041C from sleep mode Sending an email or SMS to a defined recipient when a critical level is exceeded or not reached Synchronizing time via GPS Position determ...

Page 8: ... ANT895 6ML 1 6GK5895 6ML00 0AA0 For receiving GPS position and time information SIM card 1 Any mini SIM card with a data option SITRANS LU150 analog level sensor 2 7ML5201 0FB0 Up to 5 m Digital filling level sensor 2 Available from specialist dealers Digital moisture sensor 1 Available from specialist dealers SCALANCE M816 1 2 6GK5816 1AA00 2AA2 You can also use a different router TeleControl Se...

Page 9: ...ber Note M6 programming device 1 3 6ES7718 1 0 Required for SINEMA Remote Connect Client TeleControl Server Basic Engineering You can also use other PGs PCs This application example consists of the following components Table 1 2 109739240_RTU3041C_TCSB_SINEMA_RC_DOC_V30_de pdf This document 109739240_RTU3041C_TCSB_SINEMA_RC_PROJ_V30 zip Configuration file of the RTU3041C ...

Page 10: ...hardware setup of the solution Figure 2 1 LAN 192 168 5 12 255 255 255 0 LAN 172 16 0 1 255 255 0 0 Ethernet PG PC TCSB VPN tunnel IPC SINEMA Remote Connect Server RTU3041C PG PC Client LAN 192 168 2 11 255 255 255 0 LAN X2 192 168 2 10 255 255 255 0 WAN X1 172 16 1 50 255 255 0 0 WAN static IP VPN 172 30 0 2 VPN 172 30 0 3 LAN 192 168 0 3 255 255 255 0 SCALANCE M816 SCALANCE M816 WAN dynamic IP L...

Page 11: ...5 255 255 0 SINEMA Remote Connect Client OPC UA Client RTU3041C 192 168 0 3 192 168 2 3 255 255 255 0 Access to WBM SINEMA Remote Connect Server 172 116 1 60 255 255 0 0 WAN IP address SINEMA Remote Connect Clients 172 30 0 1 172 30 255 254 255 255 0 0 Virtual IP addresses defined IP range Note If you have configured several interface cards on your PC or server e g PG PC TCSB and you cannot config...

Page 12: ... Connect the digital level sensor to the terminal block X20 5 Connect the digital moisture sensor to terminal block X21 6 Connect the analog level sensor to terminal blocks X40 and X41 For instructions on how to operate the SITRANS LU150 refer to the instruction manual https support industry siemens com cs ww en view 109739505 7 Connect the antennas to the RTU3041C 8 Connect the battery module hou...

Page 13: ...his ensures that the current time is obtained precisely 2 2 1 Configuring a SINEMA Remote Connect Server This section shows you all necessary steps to configure a SINEMA Remote Connect Server for the application described here In order to put the application example into operation the SINEMA Remote Connect Server must be installed and the web server must be accessible via the LAN interface The pro...

Page 14: ...ress that you assigned to the WAN port during installation e g 172 16 1 60 4 Depending on your browser you may need to trust a certificate or confirm a security exception 5 Log into the web server with your user data Note When you log in for the first time or after a reset to factory settings the login details are set as follows Name admin Password admin Assign a username and a new password for th...

Page 15: ...rom the drop down list 11 Set the IP address and subnet mask 12 Enable SINEMA Remote Connect is located behind a NAT device 13 Enter the WAN IP address of your router 14 Save the settings with Save 10 12 14 11 13 15 Enable the interface via Activate the interface 16 Select the LAN port from the drop down list 17 Set the local IP address 192 168 2 10 and subnet mask 18 Save the settings with Save 1...

Page 16: ...o the menu item System Address Spaces 20 Open the OpenVPN tab 21 Assign a virtual IP address to the SINEMA Remote Connect Clients by defining an IP range in the server 22 Enable the fixed IP address range 23 Select UDP as the fixed IP protocol 24 Select First as the location of the fixed IP address range 25 Save the settings with Save 19 20 22 23 24 21 25 ...

Page 17: ...l rights reserved 26 Navigate to the menu item Security OpenVPN to enable the OpenVPN protocol in the VPN server 27 Select the OpenVPN tab 28 Enable the OpenVPN protocol 29 Select WAN as the interface The OpenVPN connection to the OpenVPN clients is established via this interface 30 Save the settings with Save 26 27 28 29 30 ...

Page 18: ...can create participant groups Participant groups are also needed so that participants can communicate with each other 1 Navigate to the menu item Remote connections Participant groups 2 Click Create 3 Assign a group name e g RTU3041C 4 Enable the option Members may communicate with each other 5 Enable the option for LAN 1 so that the RTUs can reach the TeleControl Server via the LAN interface 6 Sa...

Page 19: ...ll rights reserved Creating users The SINEMA Remote Connect Client is represented as a user in the SINEMA Remote Connect Server 1 Navigate to the menu item User Accounts Users Roles Users 2 Click Create 3 Assign a unique username for the SINEMA Remote Connect Client 4 Select Password as the login method 5 Then click on Next ...

Page 20: ...2 Engineering Securely Connecting RTU3041C to TeleControl Server Basic Entry ID 109739240 V3 0 07 2021 20 Siemens AG 2021 All rights reserved 6 Add the role admin 7 Save the changes ...

Page 21: ...1 21 Siemens AG 2021 All rights reserved 8 Add the user to the group RTU3041C 9 Then click on Next 10 Enable the use of a fixed IP address 11 Assign an IP address within the previously defined IP address range e g 172 30 0 2 12 Then click on Next 10 12 11 13 Assign a password 14 Then click Finish 13 14 ...

Page 22: ...tions Devices 2 Click Create 3 Assign a unique device name for the RTU3041C 4 Assign a password 5 Select RTU303xC under Type in the drop down list 6 Select OpenVPN as the VPN protocol 7 Select Permanent as the connection type 8 Enable the use of a fixed IP address 9 Assign an IP address within the previously defined IP address range e g 172 30 0 3 10 Select the previously created group RTU3041C 11...

Page 23: ...ed during RTU configuration to establish the VPN connection This information can be found in the Device overview of the created RTU 1 Open the Device overview of the created RTU via Remote Connections Devices RTU3041C i 2 Extract the information necessary for the RTU configuration If you want to operate several RTUs you must create another device for each RTU in the SINEMA Remote Connect Server ...

Page 24: ...rd into the RTU3041C before configuring For each RTU you need a SIM card with data option You can obtain this from your mobile provider General configuration 1 Connect the RTU3041C to your Engineering Station 1 via a network cable Note If you are using multiple RTUs address conflicts may occur during initial startup because each RTU is assigned the same IP address by default Therefore during commi...

Page 25: ...c Entry ID 109739240 V3 0 07 2021 25 Siemens AG 2021 All rights reserved 5 Log in with the username admin and the password admin 6 Assign a new username and password 7 Navigate to the System menu and assign a unique station name 8 Assign the coordinates for the RTU3041C ...

Page 26: ...g Securely Connecting RTU3041C to TeleControl Server Basic Entry ID 109739240 V3 0 07 2021 26 Siemens AG 2021 All rights reserved 9 Then click Apply 10 Open the System time tab 11 Select your local time zone 10 11 ...

Page 27: ...mens AG 2021 All rights reserved 12 Then click Apply 12 13 Navigate to the LAN menu 14 Enter an IP address 192 168 2 3 and subnet mask 192 168 2 3 13 14 Note If you are running multiple RTUs on a network you must assign a unique IP address Assign an IP address according to your network settings e g 192 168 2 4 ...

Page 28: ...ing RTU3041C to TeleControl Server Basic Entry ID 109739240 V3 0 07 2021 28 Siemens AG 2021 All rights reserved 15 Then click Apply 192 168 2 3 15 16 Adjust the IP address of your Engineering PG PC in accordance with Table 2 1 again ...

Page 29: ...rights reserved 17 Navigate to the WAN menu 18 Open the Mobile wireless settings tab 19 Enable the mobile function interface 20 Enter the PIN of the inserted SIM card 21 Enable the mobile data service 22 Enter the APN of your mobile operator If necessary enter your username and password 23 Then click Apply 17 18 23 22 19 20 21 ...

Page 30: ...uring SMS email sending receiving To enable the RTU3041C to send messages and data for configurable event classes diagnostic buffer entries either as SMS or as email to an operator proceed as follows 1 Open the SMS tab 2 Enable the Allow receipt of SMS messages checkbox 3 Enable the Acknowledgment of wake up SMS message checkbox 4 Then click Apply ...

Page 31: ... Basic Entry ID 109739240 V3 0 07 2021 31 Siemens AG 2021 All rights reserved 5 Navigate to the Services menu 6 Open the Email tab 7 Enable the Active option there 8 Enter the server data of the email account that the RTU should use to send emails 9 Then click Apply ...

Page 32: ...istrator 12 Enter the phone number with country code e g 49 for Germany 13 Enter the email address for the Administrator user 14 Then click Apply Note The RTU3041C only accepts wake up SMS messages from phone numbers that are stored here 10 11 11 12 13 14 15 Open the Recipient groups tab 16 Add a new group named Administrator SMS 17 Select the type SMS 18 Enable the Administrator user 19 Then clic...

Page 33: ...41C to TeleControl Server Basic Entry ID 109739240 V3 0 07 2021 33 Siemens AG 2021 All rights reserved 20 Add a new group named Administrator Email 21 Select the Email type 22 Enable the Administrator user 23 Then click Apply 20 20 21 22 23 ...

Page 34: ...d here 3 Set the communication mode to Cyclic and specify the cycle of the communication mode e g 10 minutes for test purposes or 12 hours for the application described here 4 Enter how often the mobile wireless interface should be switched on to fetch SMS This is not necessary for the application described here Select No for this purpose 5 Enter the minimum duration of the service mode e g always...

Page 35: ...G 2021 All rights reserved Configuring the GPS functionality of the RTU3041C To enable communication between the RTU3041C and its communication partner via GPS proceed as follows 1 Navigate to the GPS menu 2 Open the General tab 3 Enable the Active checkbox 4 Select the GPS always active check box 5 Then click Apply ...

Page 36: ...ID 109739240 V3 0 07 2021 36 Siemens AG 2021 All rights reserved To enable time synchronization via GPS proceed as follows 6 Navigate to the System menu 7 Open the System time tab 8 Enable the time synchronization 9 Select GPS as the synchronization method 10 Then click Apply 10 ...

Page 37: ...on of the RTU3041C to the TeleControl Server Basic TCSB and to read it out via the OPC UA Client enable the GPS tags 11 Navigate to the GPS menu 12 Open the Tags tab 13 Click the Latitude tag 14 Enable the Active checkbox 15 Enter a name for the desired tag 16 Then click Apply 11 12 13 14 16 15 17 Repeat steps 13 16 for the tags Longitude Visible satellites and Time of last position ...

Page 38: ...r programming in the RTU3041C Before you start programming in the RTU configure the inputs outputs and memory bits 1 Navigate to the Tags menu 2 Open the Digital inputs tab 3 Click on input 0 4 Enable the Active checkbox 5 Assign the name float 6 Select that an additional update cycle is also performed in sleep mode when the value changes 7 Then click Apply ...

Page 39: ...t 1 9 Enable the Active checkbox 10 Assign the name enableReadFillLevel 11 Select that an additional update cycle is also performed in sleep mode when the value changes 12 Then click Apply 10 11 12 13 Open the Digital memory bits tab 14 Click on the 0 memory bit 15 Enable the Active checkbox 16 Assign the name fillLevel90 17 Then click Apply 13 14 15 17 16 ...

Page 40: ...cting RTU3041C to TeleControl Server Basic Entry ID 109739240 V3 0 07 2021 40 Siemens AG 2021 All rights reserved 18 Click memory bit 1 19 Enable the Active checkbox 20 Assign the name critFillLevel 21 Then click Apply 20 18 19 21 ...

Page 41: ... 0 07 2021 41 Siemens AG 2021 All rights reserved 22 Click memory bit 2 23 Enable the Active checkbox 24 Assign the name gpsPosition 25 Then click Apply 22 23 25 24 26 Open the Analog inputs tab 27 Click the analog input 0 28 Enable the Active checkbox 29 Assign the name fillLevel 26 27 28 29 ...

Page 42: ...e settling and integration time as well as the smoothing of the signal of your sensor The following settings are recommended for the SITRANS Probe LU150 sensor Settling time 30 000 ms Integration time 40 ms Smoothing Weak Note Note that settling time integration time smoothing factor must not be longer than the update mode cycle 30 31 32 Enter the sensor and process values for your application In ...

Page 43: ...the digital input enableReadFillLevel is activated This can significantly reduce power consumption 34 Enable the Diagnostics messages to diagnose the errors 35 Then click Apply 33 34 35 36 Open the Analog memory bits tab 37 Click the analog memory bit 0 38 Enable the Active checkbox 39 Assign the name maxVolume 40 Select the type Analog value 41 Enter the maximum fill level of the rainwater overfl...

Page 44: ...2021 44 Siemens AG 2021 All rights reserved 43 Click the analog memory bit 1 44 Enable the Active checkbox 45 Assign the name fillLevelPercent 46 Select the type Analog value 47 Then click Apply 43 44 46 47 45 48 Click the analog memory bit 2 49 Enable the Active checkbox 50 Assign the name distance ...

Page 45: ...ngineering Securely Connecting RTU3041C to TeleControl Server Basic Entry ID 109739240 V3 0 07 2021 45 Siemens AG 2021 All rights reserved 51 Select the type Analog value 52 Then click Apply 48 49 50 51 52 ...

Page 46: ...d a new text to be sent via SMS and email when the critical level is exceeded Name critLevelReached Text The fill level of the rain overflow basin at station x has reached a critical level Date DATE Time TIME 3 Then click Apply 4 Add a new text to be sent when the critical level is exceeded in the subject of the email Name subCritLevelReached Text Critical fill level reached at station x 5 Then cl...

Page 47: ...0 07 2021 47 Siemens AG 2021 All rights reserved 6 Add a new text to be sent by SMS and email when the level falls below the critical level Name fillLevelFallen Text The fill level of the rain overflow basin at station x has fallen below the critical level Date DATE Time TIME 7 Then click Apply ...

Page 48: ...falls below the critical level in the subject of the email Name subFillLevelFallen Text Fill level at station x has fallen below critical level 9 Then click Apply 10 Add a new text to be sent by SMS when the RTU3041C moves within a parameterized radius Name gpsPositionOK Text The last known GPS position is within the tolerance radius Date DATE Time TIME 11 Then click Apply 10 11 10 10 ...

Page 49: ...9240 V3 0 07 2021 49 Siemens AG 2021 All rights reserved 12 Add a new text to be sent by SMS when the RTU3041C moves outside a parameterized radius Name gpsPositionNotOK Text The last known GPS position is outside the tolerance radius Date DATE Time TIME 13 Then click Apply 12 12 12 13 ...

Page 50: ...s you must create a program Programming is comparable to FBD in the TIA Portal Program comparison of the current level with a critical value 1 Navigate to the Program menu 2 Assign the name Critical fill level to the network 3 Add a new function block FB1 4 Select Division as the function 5 Interconnect the parameters as follows Dividend fillLevel AI0 Divisor maxVolume AM0 Quotient fillLevelPercen...

Page 51: ...ID 109739240 V3 0 07 2021 51 Siemens AG 2021 All rights reserved 7 Select Limit value switch as the function 8 Interconnect the parameters as follows Input fillLevelPercent AM1 Output fillLevel90 DM0 Limit value 1 0 9000 Limit value 2 0 8999 9 Add a new function block FB3 below ...

Page 52: ...Entry ID 109739240 V3 0 07 2021 52 Siemens AG 2021 All rights reserved 10 Select Logical OR as the function 11 Interconnect the parameters as follows Input 1 float DI0 Input 2 fillLevel90 DM0 Output critFillLevel DM1 10 11 11 11 12 Negate input 1 13 Then click Apply 12 13 ...

Page 53: ...ng email transmission 14 Add a new network 14 15 Assign the name Send email to the network 16 Add a new function block FB1 16 15 17 Select Send email as the function 18 Interconnect the parameters as follows Trigger critFillLevel DM1 Send immediately True Recipient Administrator email Text critFillLevelReached Subject subCritFillLevelReached 17 18 18 ...

Page 54: ... All rights reserved 19 Add a new function block FB2 19 20 Select Send email as the function 21 Interconnect the parameters as follows Trigger critFillLevel DM1 Send immediately True Recipient Administrator email Text fillLevelFallen Subject subFillLevelFallen 20 21 21 22 Negate the Trigger input 23 Then click Apply 22 23 ...

Page 55: ...ng SMS transmission 24 Add a new network 24 25 Assign the name Send SMS to the network 25 26 Add a new function block FB1 26 27 Select Send SMS as the function 28 Interconnect the parameters as follows Trigger critFillLevel DM1 Send immediately True Recipient Administrator SMS Text critLevelReached 27 28 28 29 Add a new function block FB2 below it 29 ...

Page 56: ...ved 30 Select Send SMS as the function 31 Interconnect the parameters as follows Trigger critFillLevel DM1 Send immediately True Recipient Administrator SMS Text fillLevelFallen 30 31 31 32 Negate the Trigger input 33 Then click Apply 32 33 Programming GPS position 34 Add a new network 34 35 Assign the name GPS Position to the network 35 ...

Page 57: ...unction 38 Interconnect the parameters as follows Position System location Radius m 1000 Output gpsPosition DM2 Distance distance AM2 37 38 38 38 39 Add a new function block FB2 below it 39 40 Select Send SMS as the function 41 Interconnect the parameters as follows Trigger gpsPosition DM2 Send immediately True Recipient Administrator SMS Text gpsPositionOK 40 41 41 42 Add a new function block FB3...

Page 58: ...0 V3 0 07 2021 58 Siemens AG 2021 All rights reserved 43 Select Send SMS as the function 44 Interconnect the parameters as follows Trigger gpsPosition DM2 Send immediately True Recipient Administrator SMS Text gpsPositionNotOK 44 43 44 45 Negate the Trigger input 46 Then click Apply 45 46 ...

Page 59: ...under Active in the drop down list 4 Then enter the static IP address of your router in the SINEMA Remote Connect server input field 5 Select WAN under Interface in the drop down list 6 Enter the Device ID that is displayed in the device information of the SINEMA Remote Connect Server 7 Enter the password configured in the SINEMA Remote Connect Server 8 Enter the SHA256 fingerprint from the SINEMA...

Page 60: ... Server Basic Entry ID 109739240 V3 0 07 2021 60 Siemens AG 2021 All rights reserved Note The Device ID and the SHAx fingerprint can be found in the Device overview of the created RTU in SINEMA Remote Connect Server under Remote Connections Devices RTU3041C i ...

Page 61: ...guring the connection to the TeleControl Server A connection to the TeleControl Server must be established so that the RTU3041C can reach the TeleControl Server 1 Navigate to the TeleControl menu 2 Open the TeleControl Basic tab 3 Enable the Active checkbox 4 Enter the IP address 192 168 2 11 of the TeleControl server 5 Select VPN as the interface ...

Page 62: ...739240 V3 0 07 2021 62 Siemens AG 2021 All rights reserved 6 As the port number enter the IPT listener port of the TeleControl Server that you have enabled in your router 55097 by default 7 Enter a unique project number a unique station number a TeleControl password 8 Then click Apply ...

Page 63: ...1 Transmission method Event only current values Trigger Change Transfer mode Buffered transfer 12 Set the following settings for the digital input gpsPosition DM2 Transmission method Event only current values Trigger Change Transfer mode Buffered transfer 13 Set the following settings for the digital memory bit critFillLevel DM1 Transmission method Event only current values Trigger Change Transfer...

Page 64: ... the following settings for the analog input gpsLongitude GPS1 Transmission method Event only current values Trigger Change Transfer mode Buffered transfer 17 Set the following settings for the counter input visibleSatellites GPS3 Transmission method Event only current values Trigger Change Transfer mode Buffered transfer 18 Set the following settings for the counter input timeLastPosition GPS4 Tr...

Page 65: ...you cannot configure a default gateway for the TCSB add a static route to the Windows routing table 1 Start Command Prompt Desktop app as administrator 2 For example enter the following command Route add 172 30 0 0 MASK 255 255 0 0 192 168 2 10 3 Press enter Result 172 30 0 0 Target subnet VPNs defined IP range 192 168 2 10 SINEMA RC Server LAN To configure the TeleControl Server Basic proceed as ...

Page 66: ...er password with which Engineering Stations can connect to the TeleControl server The server password is not relevant for this application example but must be assigned The SMS gateway operator is not relevant for this application example 6 Then click Create Note The parameter Project number must match the parameter in Section 2 2 2 in the configuration of the connection to the TeleControl Server S...

Page 67: ...nique station number a TeleControl password Note The parameters Station number and Telecontrol password must match the parameters in Section 2 2 2 in the configuration of the connection to the TeleControl Server Step 7 10 Click OK 10 Note If you use more than one RTU you can configure all RTUs in this step To do this select Add multiple connections and assign the station data Click OK ...

Page 68: ...tch off the encryption of the Telecontrol protocol for using VPN connections Project Edit Configure connection encryption None or HC 128 11 11 11 11 12 Click Save activate and confirm the action in the drop down list 12 13 Configure the IPT listener port 55097 of the TeleControl server TCSB system TCM Listener ports IPT listener port 13 13 13 13 13 ...

Page 69: ...0 07 2021 69 Siemens AG 2021 All rights reserved The configuration of the TeleControl Server is now completed Note The connected status is only displayed when the TeleControl Server has established a connection to the RTU3041C whose configuration data has been transferred to the runtime system ...

Page 70: ...onnect Client is installed on your PC The VPN connection has been established Section 2 2 1 The configuration of the RTU3041C is loaded into the RTU Section 2 2 2 The configuration of the TCSB is completed Section 2 2 3 Note In order for the OPC UA Server of the TCSB to be accessible from the OPC UA Client the VPN connection must first be established This is necessary because the TCSB is only acce...

Page 71: ... with Table 2 1 2 Start the SINEMA Remote Connect Client 3 Connect to your SINEMA Remote Connect Server by entering the static IP address of your router the port static IP address 1443 and the login data of the previously created user see Section 2 2 1 Step 13 4 Then click Log in 5 After the successful login establish a VPN tunnel 6 After the VPN connection is established allow communication to th...

Page 72: ...109739240 V3 0 07 2021 72 Siemens AG 2021 All rights reserved 9 In the dialog double click Double click to Add Server in the Custom Discovery list area 10 In the following dialog enter the URL and the port of the OPC UA Server TCSB e g opc tcp 192 168 2 11 4852 11 Click on OK 11 10 ...

Page 73: ...t to establish a connection for example OPC SimaticNET TCSB opc tcp None None Note For test purposes you can also create the connection without exchanging certificates If you want a certificate exchange you have to accept the certificate manually in the CMT Configuration and Monitoring Tool 13 Enter the user data for the CMT Configuration and Monitoring Tool 14 Set the Connect Automatically checkb...

Page 74: ... Then confirm with OK 13 13 14 15 16 In the following dialog accept the server certificate by setting the checkbox Accept the server certificate temporarily for this session 16 The certificate is not stored in the UaExpert trusted list Note To permanently add the certificate to the UaExpert trusted list you must select Trust Server Certificate ...

Page 75: ...ting RTU3041C to TeleControl Server Basic Entry ID 109739240 V3 0 07 2021 75 Siemens AG 2021 All rights reserved 17 Then click Continue 17 18 Then locate the desired data points and drag them into the Data Access view window Result ...

Page 76: ...t only one RTU is connected to your network at a time during commissioning as each RTU is assigned the same IP address at the factory 2 If necessary change the IP address of your PG PC according to Table 2 1 so that it and the RTU3041C are in the same subnet The factory default IP address 192 168 0 3 is set in the RTU3041C 3 Wake up the RTU3041C by briefly pressing the WKUP RESET button on the RTU...

Page 77: ... 0 07 2021 77 Siemens AG 2021 All rights reserved 11 Click Load on device 11 12 The previously set password is overwritten with the password RTU3041c stored in the configuration file 13 Navigate to the System General menu 14 Assign the coordinates for your RTU3041C 15 Then click Apply 13 15 14 ...

Page 78: ...rol Server Basic Entry ID 109739240 V3 0 07 2021 78 Siemens AG 2021 All rights reserved 16 Navigate to the Operating mode menu 17 Enter the minimum duration of the service mode e g 30 seconds for the application described here 18 Then click Apply 16 17 18 ...

Page 79: ... 109739240 V3 0 07 2021 79 Siemens AG 2021 All rights reserved 19 Navigate to the Users groups menu 20 Enter the phone number with country code e g 49 for Germany 21 Enter the email address for the Administrator user 19 19 20 21 22 Change the password 23 Then click Apply 22 23 22 ...

Page 80: ... Basic Entry ID 109739240 V3 0 07 2021 80 Siemens AG 2021 All rights reserved 24 Navigate to the WAN menu 25 Open the Mobile wireless settings tab 26 Enter the PIN of the inserted SIM card 27 Enter the APN of your network operator 28 Then click Apply 24 25 27 28 26 ...

Page 81: ...o the Security menu 34 Open the VPN tab 35 Select SINEMA Remote Connect under Active in the drop down list 36 Then enter the static IP address of your router in the SINEMA Remote Connect server input field 37 Select WAN under Interface in the drop down list 38 Enter the Device ID that is displayed in the device information of the SINEMA Remote Connect Server 39 Enter the password configured in the...

Page 82: ...240 V3 0 07 2021 82 Siemens AG 2021 All rights reserved 33 34 35 37 39 41 38 40 36 42 Navigate to the TeleControl menu 43 Open the TeleControl Basic tab 44 Enter the IP address of the TeleControl Server e g 192 168 2 11 45 Enter the Telecontrol password 46 Then click Apply 42 43 46 44 45 ...

Page 83: ... Server Basic Entry ID 109739240 V3 0 07 2021 83 Siemens AG 2021 All rights reserved Note The Device ID and the SHAx fingerprint can be found in the Device overview of the created RTU in SINEMA Remote Connect Server under Remote Connections Devices RTU3041C i ...

Page 84: ...e to the LAN menu 48 Enter an IP address 192 168 2 3 and subnet mask 49 Then click Apply 192 168 2 3 47 48 49 Note If you are running multiple RTUs on a network you must assign a unique IP address Assign an IP address according to your network settings e g 192 168 2 4 50 Adjust the IP address of your Engineering PG PC in accordance with Table 2 1 again ...

Page 85: ...cify an appointment in the wake up SMS the RTU will establish a connection with its communication partner at the exact time you send the SMS 3 To do this send TELESERVICE YYYY MM DD hh mm ss to the mobile phone number of the SIM card inserted in the RTU Figure 2 3 Alarm SMS Note The telephone number from which the RTU is woken up must be stored and authorized in the RTU You can find the setting in...

Page 86: ...ollowing is assumed The configuration of the RTU3041C is loaded into the RTU see Section 2 2 2 OPC UA Server TCSB is activated see Section 2 2 3 OPC UA Client UaExpert is connected to the OPC UA Server TCSB see Section 2 2 4 To display the exact position of the RTU proceed as follows 1 To enter the GPS coordinates of the RTU3041C open Google Maps for example 2 Get the GPS coordinates of your RTU30...

Page 87: ...INEMA RC is a scalable server application that provides end to end connection management of distributed networks via the internet It coordinates the secure connection setup between the individual participants control center service technicians mechanical engineers machines or their VPN tunnel endpoints e g SCALANCE S615 SCALANCE SC 600 or SCALANCE M Communication between SINEMA RC Server and the r...

Page 88: ...ote access to the machine available The administration of all licenses and the software for the connected clients is done centrally Recurring tasks can be automated thanks to a REST API making it easy to manage even very large installations Figure 3 1 SINEMA Remote Connect https connection setup Authentication with fingerprint or certificate Network settings servers OVPN config file Set up OpenVPN...

Page 89: ...hat were configured for the current cycle Editing the program blocks Writing of outputs Saving the process data to the SD card with activated logging After the update mode the RTU falls back into sleep mode or switches to communication mode if this is configured The update and communication cycles can also run independently of each other Note In order for the RTU to transmit current values of the ...

Page 90: ...AG 2021 All rights reserved Value change at analog input AI0 Edge change at a digital input Triggering timers of program blocks e g with the pulse generator or with the on off delay Figure 3 3 Parameterization of the additional update mode Note Note that monitoring configured events will result in higher power consumption ...

Page 91: ...ntenance work Switching on the mobile wireless interface Independently of the communication cycle you can define how often the mobile wireless interface should be switched on to pick up possible wake up SMS messages No connection to the TeleControl server is established You also specify this in the web interface under Operating mode Figure 3 4 Switching on the mobile wireless interface Note Note t...

Page 92: ...ological order and transmitted to the communication partner during the communication mode Since the HMI does not support the OPC UA function HistoryRead and only the last value is always transferred this transfer type has no advantage for this example 3 2 3 Transmission Mode of the Data Points If you parameterize Event current value or Event any value as the transmission type you can additionally ...

Page 93: ...ividual support contracts Please send queries to Technical Support via Web form support industry siemens com cs my src SITRAIN Digital Industry Academy We support you with our globally available training courses for industry with practical experience innovative learning methods and a concept that s tailored to the customer s specific needs For more information on our offered trainings and courses ...

Page 94: ...ng directly and independently of time and location mall industry siemens com 4 3 Links and literature Table 4 1 No Topic 1 Siemens Industry Online Support https support industry siemens com 2 Link to this entry page of this application example https support industry siemens com cs ww en view 109739240 3 SIMATIC TeleControl RTU RTU3030C RTU30x1C https support industry siemens com cs ww en view 1097...

Page 95: ...s AG 2021 All rights reserved 4 4 Change documentation Table 4 2 Version Date Modifications V1 0 10 2016 First version V2 0 01 2019 Migration to TeleControl Server Basic V3 1 Using UaExpert as OPC UA Client V3 0 07 2021 Expansion with the GPS functions of a RTU30X1C Time synchronization Position determination ...