Configuring
6.2 Configuration via PROFINET IO
SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI
52
Operating Instructions, 04/2020, C79000-G8976-C512-03
8.
Confirm your entry with "OK".
The entry was assigned the IP address in the "Request History" area.
The entry is also displayed in the "Relation List" area.
Figure 6-2
BOOTP / DHCP server software
9.
Click the "Disable BOOTP/DHCP" button to save the IP address on the communication
module.
Result: The communication module is assigned the IP address statically.
6.2
Configuration via PROFINET IO
As of STEP 7 Basic / Professional V15.1, the RF18xC communication modules are
integrated into the TIA Portal; as of STEP 7 Basic / Professional V16, the RF18xCI
communication modules are integrated into the TIA Portal and can be linked to SIMATIC
automation systems. Integration into older STEP 7 versions is performed via a GSDML file.
The connection is made via PROFINET, the configuration via the TIA Portal and operation of
the communication module via the Ident blocks of the TIA Portal. You can further configure
the communication modules using WBM.
The GSDML file corresponding to the communication module is stored on the
communication module and can be downloaded from it via WBM. You can also find the
GSDML file at the website of Siemens Industry Online Support.