Syslog messages
B.3 List of Syslog messages
SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI
Operating Instructions, 04/2020, C79000-G8976-C512-03
203
B.3
List of Syslog messages
This section describes the Syslog messages. The structure of the messages is based on IEC
62443-3-3.
Identification and authentication of human users
Message text
{protocol}: User {user name} logged in from {ip address}.
Example
WBM: User admin logged in from 192.168.0.1.
Explanation
Valid logon information that is provided during logon.
Severity
Info
Facility
local0
Standard
IEC 62443-3-3 Reference: SR 1.1
Message text
{protocol}: User {user name} failed to log in from {ip address}.
Example
WBM: User admin failed to log in from 192.168.0.1.
Explanation
Incorrect user name or incorrect password specified during logon.
Severity
Error
Facility
local0
Standard
IEC 62443-3-3 Reference: SR 1.1
Message text
{protocol}: User {user name} logged out from {ip address}.
Example
WBM: User admin logged out from 192.168.0.1.
Explanation
User session completed - logged out.
Severity
Info
Facility
local0
Standard
IEC 62443-3-3 Reference: SR 1.1
Message text
{protocol}: Default user {user name} logged in from {ip address}.
Example
PNIO: Default user admin logged in from 192.168.0.1.
Explanation
Default user is logged on via the IP address.
Severity
Info
Facility
local0
Standard
IEC 62443-3-3 Reference: n/a (NERC-CIP 007-R5)
User account management
Message text
Authentication was enabled.
Example
Authentication was enabled.
Explanation
Authentication was enabled.
Severity
Notice
Facility
local0
Standard
IEC 62443-3-3 Reference: SR 1.3