Programming
6.3 Programming via the RS232 interface
SIMATIC RF1000
34
Operating Instructions, 02/2019, C79000-G8976-C432-04
6.3.2.3
syscmd_get_boot_status
Max. reader response time: 50 ms
Table 6- 21 Request telegram
Byte
Value
Description
0
0x0C
Without checksum
0x1C
With checksum
1
0x00
DevCode
2
0x05
CmdCode
3 ... 4
0x00
Parameter length (0 bytes)
5
0xXX
Optional checksum "BCC8" (when the value "0x1C" is set in byte 0)
Table 6- 22 Response telegram without errors
Byte
Value
Description
0
0x0C
Without checksum
0x1C
With checksum
1
0x00
DevCode
2
0x05
CmdCode
3
0x04
Parameter length (4 bytes)
4
0x00
5 ... 8
0x00
Boot status = 0x00 (OK)
9
0xXX
Optional checksum "BCC8" (when the value "0x1C" is set in byte 0)
6.3.2.4
syscmd_set_port
Max. reader response time: 100 ms
Table 6- 23 Request telegram
Byte
Value
Description
0
0x0C
Without checksum
0x1C
With checksum
1
0x00
DevCode
2
0x07
CmdCode
3
0x02
Parameter length (2 bytes)
4
0x00