Summary of Contents for SIMATIC PP17-I

Page 1: ...scription PP17 I 6 Unit Description PP17 II 7 Attach Labeling Strips 8 Spare Parts 9 Technical Data A System Messages B Hardware Test C Siemens Worldwide D Index Release 06 98 PP7 PP17 I PP17 II Push Button Panels Equipment Manual SIMATIC HMI 6AV3991 1CA00 0AB0 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 2: ...onent is in conformity with the guideline 89 392 EEC Faultless and safe operation of the product presupposes proper transportation proper storage erection and installation as well as careful operation and maintenance SIMATIC is a registered trademark of Siemens AG Some of the other designations used in these documents are also registered trademarks the owner s rights may be violated if they are us...

Page 3: ... to configure a Push Button Panel 3 Detailed information on the interrelationship between the Push Button Panel and PLC 4 Mechanical and electrical installation of the Push Button Panels 5 7 Unit description of the various Push Button Panel versions 8 Information on labelling 9 Information on spare parts Appendices Technical data system messages hardware test Please address technical questions to ...

Page 4: ...to 18 00 Tel 49 911 895 7000 Fax 49 911 895 7002 E mail simatic support nbgm siemens de Local time Mon Fri 8 00 to 17 00 Tel 1 423 461 2522 Fax 1 423 461 2231 E mail simatic hotline sea siemens com Local time Mon Fri 8 30 to 17 30 Tel 65 740 7000 Fax 65 740 7001 E mail simatic singnet com sg SIMATIC Premium Hotline chargeable SIMATIC Card required Times Mon Fri 0 00 to 24 00 Tel 49 911 895 7777 Fa...

Page 5: ...e fax polling service on 08765 93 02 77 95 00 Up to date product information and downloads for practical use can be found on the internet at http www ad siemens de support html 00 from the Bulletin Board System BBS in Nuremberg SIMATIC Cus tomer Support Mailbox on 49 911 895 7100 For calling up the mailbox you should use a modem with up to V 34 28 8 kBaud capability and set the parameters as follo...

Page 6: ...iv PP7 PP17 I PP17 II Equipment Manual Release 06 98 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 7: ...s LEDs When Using MPI Connection 2 11 2 3 2 Configuring Keys LEDs When Using PROFIBUS DP Connection 2 12 2 4 Coordinating the Push Button Panel and PLC 2 13 3 Control Bit Assignment 3 1 4 Installation 4 1 5 Unit Description PP7 5 1 6 Unit Description PP17 I 6 1 7 Unit Description PP17 II 7 1 8 Attach Labeling Strips 8 1 9 Spare Parts 9 1 A Technical Data A 1 A 1 General technical data A 1 A 2 Digi...

Page 8: ...vi PP7 PP17 I PP17 II Equipment Manual Release 06 98 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 9: ...to the LED colors Additional 24 V digital inputs and outputs All short stroke keys and digital 24 V inputs can also be individually configured as switches Integrated lamp and key test Central release input to lock all operating actions Integrated flash timing Color coding for LEDs such as red green orange Pulse extension for short stroke keys and digital 24 V inputs can be specified via parameters...

Page 10: ...lso be activated by adjusting certain parameters Each key LED digital input and output can be individually adapted according to specific requirements No special configuration software is necessary for the Push Button Panel All adjustment of the settings is carried out either directly on the Push Button Panel or by means of the PLC configuration software All adjustments to settings carried out on t...

Page 11: ...of digital outputs 16 16 Installable oper ating elements Number of 22 5 mm ele ments which can be inte grated 3 12 Release input Lock operation of the Push Button Panel Interfaces PLC connection MPI or Profibus DP Communication SIMATIC S5 Communication SIMATIC S5 PROFIBUS DP PROFIBUS DP SIMATIC S7 M7 SIMATIC S7 M7 MPI MPI PROFIBUS DP PROFIBUS DP Data transmis sion Baud rate Max 1 5 MBaud Max 12 MB...

Page 12: ...C and thus the operating status of the process being monitored When several keys are pressed simultaneously it is detected by the Push But ton Panel and the bits are set in the PLC After restarting the system following a power failure all the bits are set to 0 Additional 22 5 mm elements can be connected using the digital inputs and outputs Non connected digital inputs are automatically set to 0 T...

Page 13: ...es to test the functional capabilitity of all the keys and lamps on the Push Button Panel The Lamp Key test can be activated by the following measures in normal operation By pressing the key assigned to the Lamp Key test function by the corresponding parameter By setting the two LED bits of the key assigned to the Lamp Key test function according to the configuration The bits must be set in the PL...

Page 14: ...digital inputs can be tested in this way In order that no unwanted signals are transmitted to the PLC during the Lamp Key test the following restrictions are valid in respect of Push Button Panel operation the inputs are locked and no signal exchanges are reported to the PLC the last status of all the keys is maintained by the PLC until normal operation returns The last key operation reported to t...

Page 15: ...MPI masters 1 The following table provides an overview of the possibilities for modifying the defined system settings Intention Procedure Chap ters Modify MPI address Set MPI address on Push Button Panel 2 1 Change baud rate Change baud rate on Push Button Panel 2 1 Change data area type Change data area type on Push Button Panel 2 1 Configure Push Button Panel properties which deviate from dj d i...

Page 16: ...tion type DP Set connection type DP on the Push Button Panel 2 1 Change DP slave address Change the DP slave address on the Push Button Panel 2 1 Change baud rate Change baud rate on Push Button Panel 2 1 Configure Push Button Panel properties which deviate from Set parameter in the configu ration software 2 3 properties which deviate from pre adjusted system settings ration software DP connection...

Page 17: ...nu level and skip for ward to the next menu level The key has no func tion in the bottom menu level In configuration mode this key serves to skip back to the superordinated menu level The key has no function in the top menu level Caution Any modifications carried out to the set tings in the current menu level are not stored In configuration mode this key serves to skip for ward to the next menu le...

Page 18: ...ndicate the predefined system settings CONNECTION DP MPI SLAVE ADR BAUDRATE PP MPI ADR RACK NO BAUDRATE DATA MB DB PARAM DB PLC ADR SLOT NO HSA PLC TYPE 2 3 400 DP MPI 200 400 NUMBER OF MPI MASTER DB DW DB MW MB DEFAULT YES NO 3 187 5 KBaud 100 0 2 100 0 0 3 126 1 3 1500 KBaud 300 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 19: ...ry Byte MB or Data Block DB MW Defines the number of the first reserved memory word for the Push Button Panel DB Defines the number of the data block in which the data area for the Push Button Panel is reserved DW Defines the number of the first reserved data word for the Push Button Panel in the data block PARAM DB Defines the number of the configuring data block PLC ADR Defines the address of th...

Page 20: ... a data block must be created in the PLC which contains the configuration data for the Push Button Panel The structure of this configuring data block is depicted in Chapter 2 4 The number of the configuring data block must be specified when configuring the Push Button Panel 2 2 2 PROFIBUS DP connection When connection type PROFIBUS DP is used the Push Button Panel must be installed in the PROFIBUS...

Page 21: ...hard ware catalog under PROFIBUS DP ADDITIONAL FIELD DEVICES SIMATIC for your Push Button Panel If the corresponding entry already exists the system already con tains the GSD files In this case skip the points 2 and 3 of these instructions 2 If the respective entry is not available in COM PROFIBUS SIMATIC S5 or HW CONFIG SIMATIC S7 the GSD files relevant to your Push Button Panel must be loaded in...

Page 22: ...ct the command Update DDB Files from the menu File HW CONFIG SIMATIC S7 Select the command Update DDB Files from the menu Options After the GSD files have been correctly integrated in the system the Push Button Panel can be used in your configuration 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 23: ...ys are numbered from right to left in rows beginning at the top right moving down The value 0 deactivates the Lamp test Value range 0 to total number of keys System default setting Lamp test assigned to Key 1 top right Function keys It is possible to define whether a key on the keyboard should function as a key or switch Function momentary contact switch The corresponding bit in the PLC is set as ...

Page 24: ...for config uring the mode of an LED The diagram below clarifies the position of the control bits in a memory byte or data block Byte n Byte n 1 Control bits for LED 1 Bit 7 Bit 0 Two successive configuration bits in one configuring data block define the way in which the status of the control bits are displayed The following table illustrates the effects of the various combinations of configuration...

Page 25: ...8 1 2 2 Byte 9 0 4 4 Byte 10 0 0 0 Byte 11 0 0 0 Byte 12 Pulse extension Pulse extension Pulse extension Byte 13 Lamp test key Lamp test key Lamp test key Byte 14 Function key 1 8 Function key 1 8 Function key 1 8 Byte 15 Function digital input 1 4 Function key 9 16 Function key 9 16 Byte 16 Mode LED 1 4 Function digital input 1 8 Function of key 17 24 Byte 17 Mode LED 5 8 Function digital input 9...

Page 26: ...he GSD files in the system as described in Chapter 2 2 the configuration software COM PROFIBUS SIMATIC S5 or HW CONFIG SIMATIC S7 can be used to define all the settings for the Push Button Panel COM PROFIBUS Call in dialog box Slave properties by double clicking on the PP symbol When it appears click on button Configure HW CONFIG Select property page Configure in dialog box Object properties 该文档是极...

Page 27: ...ntioned functions a con figuring data block must be created as described in Chapter 2 4 The first byte is reserved The figure below illustrates the structure of byte n 1 The individual bits are described underneath the figure 7 6 5 4 3 2 1 0 Address n 1 Life bit Start bit Bit 0 Start bit 1 Push Button Panel has started up The bit is set by the Push Button Panel on completion of startup You can res...

Page 28: ...2 14 PP7 PP17 I PP17 II Equipment Manual Release 06 98 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 29: ...the numeration of keys LEDs and digital inputs on the Push Button Panel and their links to bits in the PLC Keys 8 1 16 9 Bit 7 Bit 0 T8 T1 T16 T9 Byte n Byte n 1 Figure 3 1 Numeration of keys on the Push Button Panel 1 16 Digital inputs Bit 7 Bit 0 DI8 DI1 DI16 DI9 Byte n Byte n 1 Figure 3 2 Numeration of the digital inputs on the Push Button Panel 3 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdf...

Page 30: ...ital outputs on the Push Button Panel The following table indicates the data area for keys LEDs digital inputs and digital outputs of the Push Button Panel in the PLC Marker area PP7 PP17 I PP17 II Keys 1 Byte 2 Bytes 4 Bytes Digital inputs 1 Byte 2 Bytes 2 Bytes LEDs 2 bytes 4 Bytes 8 Bytes Digital outputs 4 Bytes 4 Bytes Total 4 Bytes 12 Bytes 18 Bytes A data area for the entire length must be s...

Page 31: ... data in the PLC Element assignment 0 Keys 1 8 Key 1 LED 1 0 7 3 Bit Assignment Byte Digital inputs 1 4 1 4 Digital input 2 DI Digital inputs 1 4 Figure 3 5 Control bits for PP7 Structure of the data in the PLC Element assignment 0 Keys 1 8 Keys 9 16 Key 1 LED 1 Digital inputs 1 16 Digital output 10 Digital input 5 Key 15 LED 15 0 1 8 16 7 11 Bit Assignment LEDs 1 8 LEDs 9 16 Digital inputs 1 8 Di...

Page 32: ... 17 24 Keys 25 32 Key 1 LED 1 Digital output 10 Digital input 5 Key 24 LED 24 0 1 8 16 7 10 17 Bit Assignment LEDs 1 8 LEDs 9 16 LEDs 17 24 LEDs 25 32 Digital outputs 1 8 Digital outputs 9 16 Byte 1 8 16 Digital inputs 1 16 DI Digital outputs 1 16 DO Figure 3 7 Control bits for PP17 II 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 33: ...til it is absolutely dry To prevent the Push Button Panel overheating during operation ensure the air vents in the housing are not covered following installation The Push Button Panel was function tested before shipping If a fault oc curs however please enclose a full account of the fault when returning the unit Degree of Protec tion 4 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控...

Page 34: ...ded on the sides of the Push Button Panel to enable the installation of several units beside each other without leaving any gaps between them Front panel Push Button Panel Ê 3 Secure the Push Button Panel in the front panel Ë from the rear using a screwdriver Note Do not overtighten the screws to avoid damage Front panel Ë Push Button Panel Front panel thickness max 6 mm Mechanical instal lation o...

Page 35: ... similarly appropriate tool from the rear through the elongated hole Ê in the middle of the selected snap out hole Use the screwdriver to lever the metal piece out where the 22 5 mm element is to be inserted 5 Cut the foil corresponding to the opening which appears in the front section of the Push Button Panel 6 Insert the 22 5 mm element in the opening in the front of the Push Button Panel The ba...

Page 36: ...ions Connect the grounding connection of the Push Button Panel to the cabinet ground To do this use the grounding screw supplied with the Push Button Panel Push Button Panel 24 V 0 V Input Output Push Button Panel 24 V 0 V Warning No safety related functions may be realized using the Push Button Panel Cable Voltage supply Grounding con nection Connection of additional display and operating ele men...

Page 37: ... 190 mm W x H Note The installation depth of the Push Button Panel is dependent on the type of connection cable to the PLC It does not correspond to the outer dimensions of the unit Ensure the cable has a sufficient bending radius Unit dimensions Mounting cut out 5 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 38: ...mory module Display Bus connection MPI PROFIBUSĆDP Voltage supply 24 V 0 V Digital 24 V inputs DI1 Ć DI4 Figure 5 1 Element positions on the rear side of the PP7 Rear view 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 39: ...m x 190 mm W x H Note The installation depth of the Push Button Panel is dependent on the type of connection cable to the PLC It does not correspond to the outer dimensions of the unit Ensure the cable has a sufficient bending radius Unit dimensions Mounting cut out 6 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 40: ...onnection MPI PROFIBUSĆDP Voltage supply 24 V 0 V Digital 24 V inputs DI1 Ć DI16 Digital 24 V outputs DO1 Ć DO16 Release input Figure 6 1 Element positions on the rear side of the PP17 I Rear view 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 41: ...mm x 190 mm W x H Note The installation depth of the Push Button Panel is dependent on the type of connection cable to the PLC It does not correspond to the outer dimensions of the unit Ensure the cable has a sufficient bending radius Unit dimensions Mounting cut out 7 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 42: ...onnection MPI PROFIBUSĆDP Voltage supply 24 V 0 V Digital 24 V inputs DI1 Ć DI16 Digital 24 V outputs DO1 Ć DO16 Release input Figure 7 1 Element positions on the rear side of the PP17 II Rear view 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 43: ... out on a standard printer The disk supplied with this document contains a directory SLIDES in which the file SLIDES DOC is stored This is a text file in Word for Windows 6 0 format with which the labeling strips for the Push Button Panel can be printed in the correct size The following table contains the dimensional specifications for producing the labeling strips Size PP7 PP17 I PP17 II Labeling...

Page 44: ...5 mm elements PP7 0 67 0 113 8 160 6 207 4 253 0 90 4 137 2 184 0 230 8 Figure 8 3 Text positions for keyboards PP17 I and PP17 II 0 72 0 102 8 195 2 226 0 253 0 133 6 164 4 Figure 8 4 Text positions for 22 5 mm elements PP17 I 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 45: ...ferred to the new unit If the Push Button Panel memory module is defect the message EEPROM ERR appears in the display in both normal operation and hardware test mode In this case the memory module must be replaced The following spare parts are only available for the PP17 I unit Standard keyboard Electronics Front panel It is not necessary to remove the Push Button Panel from the cabinet in order t...

Page 46: ...9 2 PP7 PP17 I PP17 II Equipment Manual Release 06 98 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www gkbpx com ...

Page 47: ...ction Front panel Rear panel IP65 IP20 Weight approx kg 0 72 1 13 24 V voltage supply PP7 PP17 I PP17 II Rated voltage VDC 24 Permissible range VDC 18 to 30 Typical power consumption at 24 V with no load applied at digital outputs 0 2 A 0 4 A Starting current inrush I2t 30x10 3 A2s Fuse type internal Electronic fuse Reverse battery protection Yes Ambient conditions PP7 PP17 I PP17 II Ambient tempe...

Page 48: ... with the following standards Interference immunity EN 50082 1 PP7 PP17 II PP17 II Static discharge contact discharge EN 61000 4 2 Class 3 RF irradiation EN 61000 4 3 Class 3 Pulse modulation ENV 50204 900 MHz 5 MHz RF conduction ENV 50141 Class 3 Burst interference ENV 61000 4 4 Class 3 Radio interference EN 50081 2 PP7 PP17 I PP17 II RFI suppression EN 55011 Class A A 2 Digital inputs and output...

Page 49: ... outputs in groups of output DO1 to DO4 output DO5 to DO8 output DO9 to DO12 output DO13 to DO16 16 4 Group 1 Group 2 Group 3 Group 4 Potential isolation Short circuit protection Yes Permissible loads Resistive Lamps Inductive Max inductive power 200 mWs Output voltage With signal 0 With signal 1 Max 2 V idling Min voltage supply 3 V Output current with signal 0 with signal 1 Max 1 mA Max 500 mA p...

Page 50: ...Release input PP7 PP17 I PP17 II Potential isolation from internal logic Input voltage rated value release on entry lock on entry 24 V DC 0 5 V 15 30 V Input current with entry locked Typ 2 mA at 24 V A 3 Interface assignment Assignment of the 9 pin Sub D socket Pin Assignment 1 2 3 Data B 4 5 GND floating 6 5 V floating 7 8 Data A 9 Bus connection PROFIBUS DP MPI 5 1 9 6 该文档是极速PDF编辑器生成 如果想去掉该提示 请...

Page 51: ...f the Push Button Panel The following table should help to determine the cause of Error LED signals Signal Cause Remedy LED flashes Normal operation The unit is in Lamp Key test mode Terminate the Lamp test by releasing the corresponding key or resetting the corresponding bits in the PLC LED lights up Hardware test mode Hardware test mode is displayed Restart the unit or terminate Hard ware test m...

Page 52: ...h Button Panel PP START PROFIBUS DP connection There is a connection fault Check the network configuration and the configuration of the interface on the Push Button Panel PP START MPI connection Connection to the defined MPI ad dress cannot be established Check the following settings in the Push Button Panel interface configuration BAUDRATE PLC ADR RACK NO and SLOT NO NO PAR DB The set configuring...

Page 53: ...rves the function in the current menu level The results of the indi vidual tests appear as they are completed OK ERROR A fault has occurred The functional unit tested is defective In Hardware Test mode this key serves to skip back to the superordinated menu level The key has no function in the first menu level In Hardware Test mode this key serves to skip for ward to the next menu level The key ha...

Page 54: ... on the keyboard the corresponding LED lights up orange Terminate the function with key or EEPROM TEST EEPROM OK SPC2 TEST ASPC2 TEST SPC2 OK ASPC2 OK DIGIO TEST DI xxxx DI xxxx DO xxxx xxxx Status of the digital inputs and out puts as hexadecimal values KEY TEST Not imple mented xx Status of the release in put KEYB ID Not imple mented xxxx Keyboard identifica tion PP17 I 2010 PP17 I 4020 EXT MODU...

Page 55: ...yreuth Berlin Bielefeld Bonn Bremen Brunswick Chemnitz Coblenz Cologne Constance Darmstadt Dortmund Dresden Duisburg Düsseldorf Erfurt Essen Frankfurt am Main Freiburg Hamburg Heilbronn Karlsruhe Kassel Kempten Allg Kiel Laatzen Leipzig Lingen Magdeburg Mainz Mannheim Munich Münster Westf Nuremberg Osnabrück Regensburg Rostock Saarbrücken Siegen Stuttgart Ulm Wetzlar Wilhelmshaven Wuppertal Würzbu...

Page 56: ...ublic Siemens AG Brno Mladá Boleslav Prague Denmark Siemens A S Copenhagen Ballerup Finland Siemens Oy Espoo Helsinki France Siemens S A Haguenau Lille Seclin Lyon Caluire et Cuire Marseille Metz Paris Saint Denis Strasbourg Toulouse Great Britain Siemens plc Birmingham Walsall Bristol Clevedon Congleton Edinburgh Glasgow Leeds Liverpool London Sunbury on Thames Manchester Newcastle Greece Siemens...

Page 57: ... A Albufeira Coímbra Lisbon Amadora Matosinhos Porto Romania Siemens birou de consultatii tehnice Bukarest Russia Siemens AG or Mosmatic Moscow Siemens AG Ekaterinburg Slovak Republic Siemens AG Bratislava Slovenia Siemens d o o Ljubljana Spain Siemens S A Barcelona Bilbao Gijón Granada La Coruña Las Palmas de Gran Canaria León Madrid Málaga Murcia Palma de Mallorca Pamplona Sevilla Valencia Valla...

Page 58: ...s Technical Office Cairo Mohandessin Siemens Technical Office Alexandria EGEMAC S A E Cairo Mattaria Ethiopia Addis Electrical Engineering Ltd Addis Abeba Ivory Coast Siemens AG Abidjan Libya Siemens AG Branch Libya Tripoli Morocco SETEL Société Electrotechnique et de Télécommunications S A Casablanca Mozambique Siemens Liaison Office Maputo Namibia Siemens Pty Ltd Windhoek Nigeria Electro Technol...

Page 59: ... AG in America Argentina Siemens S A Bahía Blanca Buenos Aires Còrdoba Mendoza Rosario Bolivia Sociedad Comercial é Industrial Hansa Ltda La Paz Brazil Siemens S A Belém Belo Horizonte Brasilia Campinas Curitiba Fortaleza Pôrto Alegre Recife Rio de Janeiro Salvador de Bahia São Paulo Vitória Canada Siemens Electric Ltd Montreal Québec Toronto Chile INGELSAC Santiago de Chile Colombia Siemens S A B...

Page 60: ...utomation Division Alpharetta GA Numeric Motion Control Elk Grove Village Illinois Uruguay Conatel S A Montevideo Venezuela Siemens S A Caracas Valencia The following table lists all Siemens Companies and Representatives of Siemens AG in Asia Bahrain Transitec Gulf Manama Bangladesh Siemens Bangladesh Ltd Dhaka Brunei Brunei Darussalam Hong Kong Siemens Ltd Hong Kong India Siemens Limited Ahmedaba...

Page 61: ...stan Siemens Pakistan Engineering Co Ltd Islamabad Karachi Lahore Peshawar Quetta People s Republic of China Siemens AG Representation Beijing Guangzhou Shanghai Philippine Islands Maschinen Technik Inc MATEC Manila Qatar Trags Electrical Engineering and Air Conditioning Co Doha Saudi Arabia Arabia Electric Ltd Equipment Al Khobar Jeddah Riyadh Singapore Siemens Pte Ltd Singapore Sri Lanka Dimo Li...

Page 62: ...tative Office Hanoi Yemen Arab Republic Tihama Tractors Engineering Co Ltd or Siemens Resident Engineers Sanaa The following table lists all Siemens Companies and Representatives of Siemens AG in Australia Australia Siemens Ltd Adelaide Brisbane Melbourne Perth Sydney New Zealand Siemens Ltd Auckland Wellington Australia 该文档是极速PDF编辑器生成 如果想去掉该提示 请访问并下载 http www jisupdfeditor com 长沙工控帮教育科技有限公司 www g...

Page 63: ...e elements A 2 Connection type 2 1 2 2 MPI 2 1 2 5 2 6 2 11 2 13 PROFIBUS DP 2 2 2 5 2 6 2 12 Connection types 1 2 Contact discharge A 2 Control bit Assignment 3 1 Coordination PLC and Push Button Panel 2 13 D Data technical A 1 Data area 2 1 Data block 2 5 2 6 2 11 Data transmission Baud rate 1 3 Data word 2 5 Degree of protection 4 1 A 1 Delay A 3 Digital inputs A 2 C 2 Function 2 10 Numeration ...

Page 64: ...3 Memory module 1 2 2 3 9 1 B 2 Memory requirements 3 2 Memory word 2 1 2 5 Messages B 1 B 2 Mounting cut out 4 2 A 1 PP17 I 6 1 PP17 II 7 1 PP7 5 1 Mounting depth A 1 MPI address 2 1 2 5 2 6 MPI connection 2 1 2 5 2 6 2 11 MPI master 2 1 2 5 N Number of inputs A 2 O Operating concept 1 4 Operating elements 1 3 Operating temperature A 1 Output current A 3 Output voltage A 3 Outputs digital 1 3 1 4...

Page 65: ... 5 Slot 2 5 Snap out opening 4 3 Spare Parts 9 1 Start bit 2 13 Starting current inrush A 1 Starting Up 2 1 Static discharge A 2 Station address highest 2 1 2 5 Storage requirements 2 6 Switching frequency A 3 System messages List B 1 System settings 2 5 modify 2 1 2 2 MPI connection 2 1 PROFIBUS DP connection 2 2 T Technical Data PP17 I A 1 PP17 II A 1 PP7 A 1 Test Hardware C 1 U Unit description...