Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity Levels
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports
2 kV (Fail-Safe
Relay Output)
DC Power Ports
2.9 kVdc
Dielectric Strength
AC Power Ports
2 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
DC Power Ports
5 kV
AC Power Ports
5 kV
IEC 60255-27
HV Impulse
POE Power Ports
1 kV
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
Description
Test Levels
Severi-
ty Levels
Enclosure Contact
± 8 kV
ESD
Enclosure Air
± 15 kV
Radiated RFI
Enclosure Ports
35 V/m (80% modulation)
Signal Ports
± 4 kV @ 2.5 kHz
DC Power Ports
± 4 kV
AC Power Ports
± 4 kV
Fast Transient
Earth Ground Ports
± 4 kV
Signal Ports
2.5 kV common mode
DC Power Ports
2.5 kV common and 1.0
kV Differential Mode
Oscillatory
AC Power Ports
2.5 kV common and 1.0
kV Differential Mode
Signal Ports
5 kV (Failsafe Relay)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV (Failsafe Relay Output)
DC Power Ports
2.9 kVdc
Dielectric Strength
AC Power Ports
2 kV
Damped Oscillat-
ing Magnetic Field
Enclosure Ports
100 A/m (peak) for 1 s
(100 kHz and 1 MHz)
5
Environmental Type Tests
Test
Description
Test Levels
Severity Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40
°F), 16 Hours
46
RUGGEDCOM RST2228P