Installing Device
2.4 Connecting the Failsafe Alarm Relay
To mount the device to a panel, do the following:
1. Place the device against the panel and align the adapters with the mounting
holes.
1
1
2
1
Screw
2
Panel/DIN Rail Adapter
Figure 2.3
Panel Mounting
2. Install the supplied screws to secure the adapters to the panel.
2.4
Connecting the Failsafe Alarm Relay
The failsafe relay can be configured to latch based on alarm conditions. The NO
(Normally Open) contact is closed when the unit is powered and there are no active
alarms. If the device is not powered or if an active alarm is configured, the relay
opens the NO contact and closes the NC (Normally Closed) contact.
Note
Control of the failsafe relay output is configurable through RUGGEDCOM RS416 . One
common application for this relay is to signal an alarm if a power failure occurs. For
more information, refer to the
RUGGEDCOM RS416 User Guide
for the RUGGEDCOM
RS416.
The following shows the proper relay connections.
14
RUGGEDCOM RS416
Installation Manual, 04/2021, C79000-G8976-1018-10