1 Technical Description, Installation Guidelines, Operation
17
IE/AS
−
INTERFACE LINK PN IO
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000
−
G8976
−
C216
−
03
1.5
Installation Guidelines and Installing the Module
!
Caution
Noise immunity / grounding
To ensure the immunity of the IE/AS-INTERFACE LINK PN IO, the IE/AS-i LINK,
the AS-i power supply unit and the power supply of the IE/AS-i LINK must be
grounded according to the regulations.
Notice
If you do not adhere to the EMC directive
2004
/
108
/EC (CE) when setting up
sy
stems and devices, this can lead to connection aborts in communication between
the PROFINET IO controller and the IE/AS-INTERFACE LINK PN IO.
Possibilities
The IE/AS-i LINK has type of protection IP 20.
You can install the IE/AS-i LINK on a standard rail (DIN rail complying with EN
50022).
Ground the DIN rail over as short a distance as possible and with low inductance.
If the rail is installed in a cabinet, make sure that it makes good contact over a
large area with the grounded mounting plate.
Installation on a DIN Rail
If you decide to install a module on a DIN rail, please note the following points:
1. The module is placed on the rail from above and then pushed down until the
catch at the bottom of the module snaps into position.
2. Other modules can be arranged to the left and right of the module.
Removing the Module from the DIN Rail
To remove the module from the DIN rail, follow the procedure below:
1. When removing the module from the DIN rail, the power supply and signal
cables must first be removed.
2. After the cables have been disconnected, press down the catch on the base of
the device using a screwdriver and pull the module out of the rail towards the
top.