Technical Specifications
Feature
Explanation/Values
S
Relative humidity
Max. 95% at +25
°
C
Construction
S
Type of protection
IP 20
S
Dimensions (W x H x D) in mm
90 x 132 x 85.5
S
Weight
approx. 380 g
Receptacle for optional C-PLUG
Full graphics display and 6 control buttons
128 x 64 pixels
1.4
Approvals
Table 1-2
Description of the Approvals
c
−
UL
−
us
UL 508
CSA C22.2 No. 142
c
−
UL
−
us for hazardous locations
UL 1604, UL 2279PT.15
CL. 1, Div. 2 GP.A.B.C.D T4
CL. 1, Zone 2, GP.IIC, T4
CL. 1, Zone 2, AEx nC IIC T4
FM
FM 3611
CL. 1, Div. 2 GP.A.B.C.D T4
CL. 1, Zone 2, GP.IIC. T4
Ta: 0...+60
°
C
C
−
TICK
AS/NZS 2064 (Class A)
CE
EN 61000
−
6
−
2, EN 61000
−
6
−
4 (replaces
EN 50081
−
2)
ATEX Zone 2
EN 60079
−
15:2005, EN 60079
−
0:2006
II 3 G EEx nA II T4
KEMA 08 ATEX 0003X
Note
The current approvals are printed on the module.