8 Using the Data Record Interface
127
IE/AS
−
INTERFACE LINK PN IO
as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000
−
G8976
−
C216
−
03
8.2.1
AS-i Line Calls
8.2.1.1
Store_Actual_Parameters
Meaning
This call writes the current parameters of the AS-i slaves from the volatile memory
of the AS-i master to its retentive memory. If the C-PLUG is inserted, the data is
written only to the C-PLUG. Existing value are overwritten, in other words, the
parameters of all AS-i slaves are configured.
In the factory setting, the bits of the AS-i slave parameters on the AS-i master all
have the value 1.
The RecordDataWrite service
−
index 7
does not contain any user data.
For information on “parameters” and the IDs of the “Configuration” (I/O
configuration, ID code, ID1 code and ID2 code) /5/.
Exceptions
There are some AS-i slave types with which the AS-i master itself manages the
slave parameter assignment. The configured parameters for these AS-i slaves are
always the same F
H
.