Application and functions
1.2 Communication services
CP 443-5 Extended
Manual, 11/2018, C79000-G8976-C162-09
11
●
S7 communication and PG/OP communication
–
PG functions with uploading / downloading of FM modules, configuration / diagnostics
and routing
Note on routing: Dynamic switchover to alternative paths (for example if there is a
problem on one of the possible transmission paths) is not supported.
–
Operator control and monitoring functions (HMI)
–
Download S7 connections and gateways in RUN.
–
Client and server for data exchange on S7 connections using communications
function blocks (faulttolerant S7 connections also possible)
●
Timeofday synchronization via PROFIBUS
–
The CP forwards timeofday synchronization frames from the LAN to the station (CPU
= time slave) or from the station to the LAN (CPU= time master).
Another option is for this station to be synchronized via a different LAN. The timeofday
synchronization frame must be forwarded over PROFIBUS for the synchronization of
further stations.
–
The CP supports time stamping of distributed process signals in conjunction with the
IM 153.
–
Timeofday status value (standard/daylight saving time switchover, synchronization
status).
●
Data record routing
You can use the CP as a router for data records intended for field devices (for example
DP slaves). SIMATIC PDM (Process Device Manager) is a tool that creates data records
of this type for assigning parameters to field devices.
The services of the CP 4435 Extended module listed above can be used independently at
the same time.
Replacing a module without a programming device
When installing the CP 4435 Extended, the configuration data of the CP is always stored in
the CPU. This means that replacing modules is possible without having to download the
configuration data from the PG.
Storage of the configuration data is protected from power failure by the battery backup or the
flash memory card in the CPU.
See also
Converting older systems (Page 14)