Configuration
3.6 Reaction of the CP 243-1 to configuration errors
CP 243-1
Operating Instructions, 03/2012, C79000-G8976-C244-02
91
If you want to make use of the free connections on your S7-300 or S7-400 system, the client
end must still be configured for each of these connections. In STEP 7 Micro/WIN 32, there is
no difference in the use of such connections and communication via connections that were
configured on the S7-300 or S7-400 system. Here, you simply need to remember that, with
free connections, the first byte of the TSAP via which such connections operate on S7-300
and S7-400 systems must always have the value 0x03. The second byte of the TSAP is
derived in a way similar to the procedure described above from the rack and the slot number
of the CPU used in your S7-300 or S7-400 system. This means that, with a free connection,
the communication access point on the S7-300 or S7-400 system is always located on the
CPU and not on the Ethernet communications processor.
Note
S7-200 systems do not support free connections. This means that, with an S7-200 system,
you will always have to configure each connection regardless of whether your system is
being used as a client or a server.
3.6
Reaction of the CP 243-1 to configuration errors
When the CP 243-1 detects an invalid configuration, it tries to obtain its TCP/IP address
parameters (IP address, subnet mask and IP address of the gateway) via a BOOTP/DHCP
service. The CP 243-1 continues to attempt this for approximately 1 minute. When it fails to
receive a reply from a BOOTP/DHCP service within this time or the reply is invalid or
contains errors, the red LED ("SF") flashes for approximately 30 seconds. This procedure
continues cyclically until the CP 243-1 either finds a valid configuration in the memory of the
S7-200 CPU or receives a valid reply from a BOOTP/DHCP server.
When the CP 243-1 receives a valid BOOTP response, it configures itself as explained
below:
●
IP address, subnet mask and IP address of the gateway are taken from the
BOOTP/DHCP response
●
The transmission type is set to "Autonegotiation" (automatic setting).
●
The monitoring time for connections (keepalive) is set to 30 seconds
With this configuration, the CP 243-1 is then able to access the S7-200 CPU via Ethernet
with STEP 7 Micro/WIN 32. A new valid configuration can now be obtained in this way.
Communication with other controllers is not possible in this status. After a reset, the CP 243-
1 then adopts the settings of the new configuration.
Note
Autonegotiation (automatic setting) mode will only work when all connected network
components support this mode.
Summary of Contents for SIMATIC NET CP 243-1
Page 6: ...Preface CP 243 1 6 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 10: ...Table of contents CP 243 1 10 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 104: ...Programming 4 5 ETHx_FTPC CP 243 1 104 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 124: ...Certification CP 243 1 124 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 138: ...Sample program CP 243 1 138 Operating Instructions 03 2012 C79000 G8976 C244 02 ...
Page 142: ...Index CP 243 1 142 Operating Instructions 03 2012 C79000 G8976 C244 02 ...