
Process interfacing via an automation system (PLC, PC)
9.4 Control with FB 79
SIMATIC MV500
172
Operating Instructions, 03/2021, C79000-G8976-C494-05
9.4.1
Assignment of the interfaces relevant to PROFINET IO
Control/status byte
Table 9- 33 Assignment of control bytes (input signals)
Bit
Signal
Description
0
DISA
Disable
Disables manual keyboard input, program selection and program sav-
ing, error acknowledgment, starting the optical reader
1
SEL0
1)
Select 0
Program selection bit 0
2
SEL1
1)
Select 1
Program selection bit 1 (with TRN = 0) / save program (with TRN = 1)
3
SEL2
1)
Select 2
Program selection bit 2
4
SEL3
1)
Select 3
Program selection bit 3
5
TRN
1)
Save program
Saves new program.
6
TRG
Trigger
Processing starts on a positive edge.
7
RES
Reset
Reset error.
1)
The signals only work if "DISA = 1".
Table 9- 34 Assignment of status byte (output signals)
Bit
Signal
Description
0
IN_OP
In operation
•
0: Error message is displayed.
•
1: Optical reader functional, no error
1
TRD
Program saved
•
In run:
–
0: Selected program is not saved.
–
1: Selected program has been saved.
•
With Save program (TRN = 1)
–
0: Save program active
–
1: Acknowledgment signal (RDY = 0)
2
RDY
Ready
•
0: Startup of the optical reader or optical reader in the "Stop"
•
1: Optical reader in "Start"
Summary of Contents for SIMATIC MV500
Page 10: ...Preface SIMATIC MV500 10 Operating Instructions 03 2021 C79000 G8976 C494 05 ...
Page 16: ......
Page 28: ......
Page 32: ......
Page 92: ......
Page 114: ......
Page 148: ......
Page 244: ......
Page 254: ......
Page 260: ......
Page 292: ......
Page 294: ...Service Support SIMATIC MV500 294 Operating Instructions 03 2021 C79000 G8976 C494 05 ...