Technical specifications
10.4 Specifications
Mobile Client900RXA
Operating Instructions, 07/2015, A5E36360099-AA
147
Note
In the following cases, ensure that no humidity can settle on or in the HMI device:
•
Transportation of the HMI device in low temperatures
•
Under extreme temperature variations
The HMI device must have acquired room temperature before it is put into operation. Do not
expose the HMI device to direct radiation from a heater in order to warm it up. If dewing has
developed, wait approximately four hours until the HMI device has dried completely before
switching it on.
The following points must be adhered to in order to ensure a fault-free and safe operation of
the HMI device:
●
Proper transportation and storage
●
Proper installation and mounting
●
Careful operation and maintenance
The warranty for the HMI device will be deemed void if these stipulations are not heeded.
10.4.5
Ambient conditions during operation
Mechanical environmental conditions
The following tables contain the validated and maximum permissible mechanical
environmental conditions- in the form of sinusoidal vibrations - for the Mobile Client and
Connection box.
Mobile Client
Duration
Effect
Tested for
10 ≤ f ≤ 57 Hz
Amplitude 0.15 mm
Vibration resistance, IEC 60068-2-6
9 ≤ f ≤ 150 Hz
Constant acceleration 2 g
11 ms
Acceleration 25 g
Shock resistance, IEC 60068-2-27
Connection box
Duration
Effect
Tested for
5 ≤ f ≤ 9 Hz
Amplitude 7 mm
Vibration resistance, IEC 60068-2-6
9 ≤ f ≤ 150 Hz
Constant acceleration 2 g
11 ms
Acceleration 15 g
Shock resistance, IEC 60068-2-27