Installing the S7-400
2-29
S7-400 and M7-400 Programmable Controllers Hardware and Installation
A5E00069481-04
Example for Determining the Type of Cabinet
The following example clarifies the maximum ambient temperature which is
permissible for a particular power dissipation with various types of cabinet.
The following equipment configuration is to be installed in a cabinet:
1 central rack
150 W
2 expansion racks of 150 W power dissipation each
300 W
1 load current power supply under full load
200 W
Total power dissipation
650 W
From Figure 2-2, with a total power dissipation of 650 W, the ambient temperatures
obtained are as follows:
Type of Cabinet
Max. Permissible Ambient
Temperature
Closed, with natural convection and forced circulation
(Curve 3)
(no operation possible)
Open, with through-ventilation (Curve 2)
approx. 38
°
C
Closed, with heat exchanger (Curve 1)
approx. 45
°
C
Dimensions of Cabinet
To determine the dimensions of a cabinet suitable for assembling an S7-400, you
must take the following into account:
•
Space requirement of the racks
•
Minimum clearances between racks and cabinet walls
•
Minimum clearances between racks
•
Space requirement of cable ducts or fan subassemblies
•
Locations of rails