Technical specifications
9.3 Fail-safe mode
KP8, KP8F
88
Operating Instructions, 10/2010, A5E03284305-01
Power supply
Parameter
Value
Comment
Hardware Fault Tolerance 0
–
Classification
A
–
Architecture
1oo1D
–
Failure mode
Detected
Undetected
Dangerous process value
22.50 FIT
0.22 FIT
Due to failures in the power supply
Failure Mode Diagnostic
Detected
Undetected
No error signaling or no safe
values
0 FIT
0 FIT
Calculation according
IEC13849:2006 CAT4
Diagnostic Coverage
99.03 %
–
Diagnostic test interval
< 10 ms
Voltage monitoring in hardware
Safe Failure Fraction
99.84 %
–
Fail-safe mode for 1oo1 evaluation
● In accordance with IEC 61508:2010
Systematic Capability
SIL3
Mode of operation
High and low demand mode
Meantime to Restoration (MTTR)
100 h
Probability of a dangerous failure per hour
(PFH)
5.95 × 10
–10
1/h
Probability of a dangerous failure on demand
(PFD)
2.61 × 10
–5
Safe Failure Fraction (SFF)
99.19 %
Diagnostic test interval
15 ms
Proof Test Interval
10 y
Lifetime
10 y
● In accordance with IEC 13849:2006
Meantime to Failure (MTTF
d
)
560 y
Meantime to Restoration (MTTR)
100 h
Diagnostic Coverage (DC
avg
)
98.90 %
Performance Level
d
Category
3
● In accordance with EN 954-1:1996
Category
3