Technical specifications
9.2 Technical specifications
KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01
85
KP8 - digital inputs/outputs
Connectable
Keys, switches
Number of digital inputs/outputs, standard mode 8
Electrically isolated from internal logic
No
Input voltage
Nominal value
With "0" signal
With "1" signal
+24 VDC
0 … +5 V
15 … 30 V
Input current for signal "1"
Typically 5 mA for 24 V
Delay in the digital inputs/outputs
0.3 ms
Connection mechanical switches
Yes
Bounce time
≤ 10 ms
Permitted resistive loads
Lamp load, permissible
0,1 A
2 W
Energy, inductive ( max.)
200 mWs
Output voltage
With "0" signal
With "1" signal
Max. 2 V no load
Min. supply voltage –3 V
Output current
With "0" signal
With "1" signal
Max. 1 mA
Cumulative current for all outputs 800 mA
Switching frequency, max. at
Resistive load
Lamp load
100 Hz
8 Hz
KP8 - fail-safe digital inputs/outputs
Additionally, with KP8F, the following applies for the fail-safe digital inputs:
Number of fail-safe digital inputs
2
Number of fail-safe outputs
Corresponding to PROFIsafe process values
Cable length
Unshielded cable, maximum
Shielded cable, maximum
1 m
3 m
Response time for
1oo1 and 1oo2 if there are no faults
6 to 22 ms
Response time for
1oo1 and 1oo2 in the event of a fault
10 to 27 ms
Acknowledgment time in safety mode
15 to 35 ms
Signal duration, minimum
22 ms