Operating KP8F in a fail-safe manner
7.4 Repair error and reintegrate
KP8, KP8F
76
Operating Instructions, 10/2010, A5E03284305-01
Diagnostics function
Error code
Scope of diagnostics functions
Short-circuit
0x01
Channel
Configuration error
0x10
Module
Communication error
0x13
Module
Discrepancy error
0x19
Channel
Non-permissible sensor evaluation
0x1C
Module
PROFIsafe address deviation
0x1D
Module
Serious error
0x1E
Module
Version conflict
0x1F
Module
You have the option of reading the diagnostics functions in the standard program by calling
SFB 52 or SFB 54. For detailed information, refer to the "System and Standard Functions"
reference manual.
Diagnostics of PROFIsafe errors
When diagnosing PROFIsafe errors, address the "DIAG" variable of the F-I/O DB. Detailed
information about the F-I/O-DB can be found in the Programming and operation manual "S7
Distributed Safety - Configuring and Programming"
HMI device with a serious error
If a serious error in the HMI device leads to its failure, the HMI device reacts as follows:
● The connection to PROFINET will be interrupted and the fail-safe channels will be
rendered passive.
● No diagnosis will be transmitted from the HMI device.
In STEP 7 in module diagnostics, the standard diagnosis "Module interrupted" or "Module
missing" will be reported.
7.4
Repair error and reintegrate
Remedy
The error correction of the HMI device should be undertaken depending on the type of error
recognized:
Error
Possible causes of error
Remedy
Short-circuit in the sensor
Eliminate the short-circuit.
Cross-circuit in the sensor
Eliminate the cross-circuit.
Short-circuit
Internal error
Replace the HMI device.