In the following image, the slot that must be set is labeled in red.
Procedure
1.
Double click in the properties window on slot 2.
The "Properties – F-DI" dialog box opens.
2.
Open the "Addresses" tab.
In the "Inputs" and "Outputs" groups, the start values of the address areas are set
depending on the controller used. The signals of the F channels of the HMI device are
mapped in these address ranges.
Parameter
Meaning
Inputs > Start
Start of address range in which the safety-relevant usage data of
the HMI device are mapped.
Inputs > Process Image
Process image to which the address range belongs.
This parameter cannot be entered with a controller of the
SIMATIC CPU 300 type.
Outputs > Start
Start of address range in which the safety-relevant usage data of
the HMI device are mapped.
Outputs > Process Image
Process image to which the address range belongs.
This parameter cannot be entered with a controller of the
SIMATIC CPU 300 type.
3.
Check the default entry of the addresses for "Start".
If necessary, change the address range.
4.
Select the "Parameters" tab.
5.
Open the "Parameters > Device-specific Panels > Evaluation of the Sensor" directory.