Installing and connecting the device
3.2 Mounting the device
SIMATIC IPC327G
22
Operating Instructions, 09/2021, A5E51366275-AA
•
All the external circuit of the device must be safe extra low voltage (SELV) or protective
extra-low voltage (PELV) circuit.
•
This device is designed for use in a normal industrial environment. Without additional
protective measures (such as the provision of clean air), SIMATIC Box PCs may not be
operated in harsh environments that are subject to caustic vapors or gases.
Possible mounting types of the device:
Mounting on a standard rail
Wall mounting
Position of the interfaces
For standard rails, the interface side of the device can point either up or down. In the case of
wall mounting, the interface side of the device can point up, down, to the left or to the right.
The position of the interface side is determined by the mounting of the mounting bracket.
Fasten securely
NOTICE
Insufficient load carrying capacity
If the mounting surface for wall and vertical mounting does not have sufficient load carrying
capability, the device may fall down and be damaged.
Ensure that the mounting surface on the wall can bear four times the total weight of the
device, including fixing elements.