SIMATIC IOT2050 Starterkit
10
Product Information, 06/2021, A5E50831253-AA
Mounting the device
3
3.1
Mounting instructions
Note the following:
•
The device is approved for indoor operation only.
•
For installation in a cabinet, observe the SIMATIC setup guidelines
http://support.automation.siemens.com/WW/view/de/1064706
) as well as the relevant
DIN/VDE requirements or the applicable country-specific regulations.
•
When the device is used in the area of Industrial Control Equipment in accordance with
UL61010-2-201, note that the device is classified as "Open equipment".
•
Siemens recommends you use 0.6 Nm tightening torque to install the mounting clamps
and brackets.
Fasten securely
NOTICE
Insufficient load carrying capacity
If the mounting surface for wall mounting does not have an enough load-bearing capacity,
the device may fall and be damaged.
Ensure that the mounting surface on the wall can bear four times the total weight of the
device, including fixing elements.
NOTICE
Incorrect fixing elements
If you use anchors and screws other than those specified below for wall mounting, safe
mounting is not guaranteed. The device can fall and may be damaged.
Only use the anchors and screws specified in the following table.
Material
Bore diameter
Fixing element
Concrete
Select according to the specifi-
cation of the mounting ele-
ments used
•
Anchor,
∅
6 mm, 40 mm long
•
Screw,
∅
4 mm, 40 mm long
Plasterboard,
(at least 13 mm thick)
Toggle plug,
∅
12 mm, 50 mm
long
Metal,
(at least 2 mm thick)
•
Screw M4 × 15
•
M4 nut