7-1
IM 178-4
C79000-G7076-C178-01
Diagnostics
7.1
Status and Diagnostic LEDs
2 diagnostic LEDs (red) and 13 status LEDs (green) on the front panel of the
module provide information about the state of the IM 178-4.
S
The SF diagnostic LED (red, group error) basically indicates the status of the
hardware.
S
The BF diagnostic LED (red, bus error) provides information about the
connection to PROFIBUS DP.
S
The ON status LED (green) indicates that the module is ready for operation.
S
The status LEDs 0I0, 0I1, 0I2, 0Q0, 0Q1, 0Q2, 1I0, 1I1, 1I2, 1Q0, 1Q1, 1Q2
indicate the state of the digital inputs and outputs.
IM 178-4
Table 7-1
ON Status LED and Diagnostic LEDs on the IM 178-4
SF
BF
ON
SF: red
BF: red
ON: green
LEDs
Meaning
Remedy
ON
BF
SF
g
y
Hardware defect on the IM 178-4.
The module is defective and must be
replaced.
*
*
The voltage is applied to the IM 178-4,
the module has detected no hardware
error.
–
*
The IM 178-4 has incorrect parameters
– there is no data exchange between
the DP master and IM 178-4.
Causes:
S
Check the PROFIBUS address.
S
Check the IM 178-4.
S
Check the configuration and
parameter assignment.