Migration of the IM 151/CPU
D-4
ET 200S Interface Module IM 151/CPU
A5E00058783-01
Porting with Packed Addresses
If FBs with packed I/O addresses are copied to the IM 151/CPU, the packed
addresses there can no longer be assigned to the I/Os of the I/O modules locally
because the CPU of the IM 151/CPU cannot work with packed addresses. This
requires rewiring of the corresponding FBs. Rewiring corresponds to ”unpacking”
the addresses.
I1.0
I1.1
I1.2
I1.3
O1.0
O1.1
DI_1_module
DI_2_module
Figure D-2
Example: FB with Packed Addresses
Rewiring
The following blocks and address IDs can be reassigned:
Inputs, outputs
Memory markers, timers, counters
Functions, function blocks
Proceed as follows to rewire the signals:
1. In SIMATIC Manager, select the “Blocks” folder, which contains the blocks with
the packed addresses that you want to port to the IM 151/CPU.
2. Choose Options
Rewire.
3. Enter the desired replacements in the displayed “Rewiring” dialog box in the
table (old address ID/new address ID).
Table D-2
Example: Replacements under Options
Rewire
Old Address ID
New Address ID
1
I 1.2
I 2.0
2
I 1.3
I 2.1
Summary of Contents for SIMATIC IM 151/CPU
Page 6: ...Important Information vi ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 14: ...Contents xiv ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 42: ...ET 200S in the PROFIBUS Network 3 12 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 68: ...Commissioning and Diagnostics 4 26 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 98: ...Technical Specifications 6 8 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 108: ...Cycle and Response Times 7 10 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 190: ...Execution Times of the SFCs and SFBs C 4 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 196: ...Migration of the IM 151 CPU D 6 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...