Configuration Frame and Parameter Assignment Frame for the ET 200S
A-5
ET 200S Interface Module IM 151/CPU
A5E00058783-01
Configuration Frame with the Default Setting for Address Areas
If you don’t parameterize the IM 151/CPU and therefore don’t specify any address
areas for data transfer with the DP master, the IM 151/CPU will start up after
commissioning with a default setting on the PROFIBUS-DP.
In the figure below you will find the configuration frame for the default setting:
16 words of input data; unit consistency (i.e. word)
16 words of output data; unit consistency (i.e. word)
Table A-4
Structure of the Configuration Frame with Default Setting for the Address Areas (Normal
Identifier Format in Accordance with AKF)
Configured
Address
Areas
Byte
1.
0
0
0
0
0
0
0
0
2.
0
0
0
0
0
0
0
0
3.
0
0
0
0
0
0
0
0
4.
7
0
Bit no.
6
4
5
3
1
2
Length of the input data: 16 words
Length specified in words
Consistency over words
Input data:
0 1
1
0
1 1
1
1
5.
7
0
Bit no.
6
4
5
3
1
2
Length of the output data: 16 words
Length specified in words
Consistency over words
Output data
0
1
1
0
1 1
1
1
Summary of Contents for SIMATIC IM 151/CPU
Page 6: ...Important Information vi ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 14: ...Contents xiv ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 42: ...ET 200S in the PROFIBUS Network 3 12 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 68: ...Commissioning and Diagnostics 4 26 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 98: ...Technical Specifications 6 8 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 108: ...Cycle and Response Times 7 10 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 190: ...Execution Times of the SFCs and SFBs C 4 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 196: ...Migration of the IM 151 CPU D 6 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...