![Siemens SIMATIC IM 151/CPU Manual Download Page 113](http://html.mh-extra.com/html/siemens/simatic-im-151-cpu/simatic-im-151-cpu_manual_1265361113.webp)
*HWWLQJ6WDUWHG
Getting Started - ET 200S-IM 151/CPU Interface Module
A5E00058783-01
8-5
6WHS3XWWLQJWKH(76,0&38LQWR2SHUDWLRQ
6WDJH
'HVFULSWLRQ
1
Make sure that the mode selector is at
STOP.
Switch on the lowest DIP switch (for stand-
alone operation) and the 4th DIP switch from
the bottom (for PROFIBUS-DP address 4) on
the IM 151/CPU.
Make sure that the other DIP switches are off.
2
Switch on the PS of the IM 151/CPU.
Result:
•
The
DC24V
LED lights up on the PS.
•
The
PWR
and the
SF LED light up on the PM.
•
All the LEDs light up on the IM 151/CPU, the
BF and the RUN LEDs go out, and the STOP
LED begins to flash slowly. The IM 151/CPU is thus requesting a memory reset.
3
Briefly press down the mode selector of the IM 151/CPU to MRES. The
STOP LED begins to
flash rapidly and then comes on continuously. This indicates that the memory reset has been
completed.
The
SF LEDs on the PM and IM 151/CPU go out.
4
Operate the two switches connected to the DI. When you operate the switch on terminals 1
and 3, the
1 LED lights up.
When you operate the switch on terminals 5 and 7, the
5 LED lights up.
5
Switch on your programming device, and start SIMATIC Manager on the Windows desktop.
6a
Click Options in SIMATIC Manager, and then choose the Setting PG/PC Interface menu
command. Configure the programming device/PC interface as follows:
6b
Note: The communication processor may have a different name in your programming device.
Make sure that the PROFIBUS version is set.
7
Apply the settings with OK, and close the Setting the PG/PC Interface program.
Summary of Contents for SIMATIC IM 151/CPU
Page 6: ...Important Information vi ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 14: ...Contents xiv ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 42: ...ET 200S in the PROFIBUS Network 3 12 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 68: ...Commissioning and Diagnostics 4 26 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 98: ...Technical Specifications 6 8 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 108: ...Cycle and Response Times 7 10 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 190: ...Execution Times of the SFCs and SFBs C 4 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...
Page 196: ...Migration of the IM 151 CPU D 6 ET 200S Interface Module IM 151 CPU A5E00058783 01 ...