Commissioning the device
4.3 Parameter assignment for Comfort Panel
Comfort Panels
150
Operating Instructions, 07/2017, A5E36770603-AB
The following functions are also available:
●
A scan function to list the HMI devices and PLC in the subnet.
●
Filter function for the scan results
●
Check assignment of IP addresses and device names for HMI devices and PLCs.
●
Project IP addresses and device names for HMI devices and PLCs can be restored.
Assigning IP address and device name
You can use the "Assign IP" function to edit the IP address and device name of target
devices in the subnet of your HMI device. The target device can be a controller or another
HMI device.
Requirement
●
The Control Panel is open.
●
For HMI devices, the following applies: The project that runs on the target device is
closed.
●
For controllers, the following applies:
–
The controller is of type S7-300, S7-400, S7-1200 or S7-1500.
–
HMI access is allowed in the settings.
–
The controller is in "STOP" state.
●
Your system administrator has provided you with the necessary information.
Procedure
1.
Open the "Service & Commissioning" dialog using the "Service & Commissioning" icon.
2.
Change to the "IP Config" tab.
①
Button for changing IP address and device name
②
Button for changing the configured communication connections