Wiring
4-14
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
4 digital inputs (DI1...4)
All inputs have equal priority. Switching functions are allocated to an input number
by way of machine data; input polarity is selected in the same way (starting and
shutdown slopes).
These fast inputs are PLC-compatible (24 V current-sourcing). Switches or con-
tactless sensors (2-wire or 3-wire sensors) can be connected.
Possible uses include:
S
As reference-point switches
S
As switches for external Start/Stop, external block change
S
As touch probes
See Section 5.3.1 for further applications.
Table 4-6
Electrical parameters of digital inputs
Parameters
Value
Unit
Comment
1 signal, voltage range
11
−
30
V
1 signal, power consumption
6
−
15
mA
0 signal, voltage range
−
3
−
5
V
or input open
Signal delay 0
→
1
15
µ
s
Signal delay 1
→
0
150
µ
s
“Controller message” (RM) input
One message signal from the drive power section can be connected to the
“RM_P/RM_N” terminals.
The message signal is specified in MD37 (see Section 5.3.1) and can be one of
the following (see Section 9.7):
S
Servo controller ready (alternative to connector X2)
S
Current-sourcing pattern zero signal for reference point approach
S
Zero pulse, external (e.g. reference point switch signal) for reference point ap-
proach
Note
The “controller message” input is configured as an isolated optical coupler input.
This allows both a current-sourcing and a current-sinking output of the power sec-
tion to be connected. For details about wiring see
Summary of Contents for SIMATIC FM 353
Page 22: ...Product Overview 1 12 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 32: ...Installing and Removing 3 6 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 282: ...Description of Functions 9 82 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...
Page 354: ...User Data Block AW DB B 16 FM 353 Stepper Drive Positioning Module 6ES7 353 1AH01 8BG0 ...