Configuring And Operating The SIMATIC Field PG
3-20
SIMATIC Field PG Manual
A5E00075760-04
3.12
Connecting the Field PG to a SIMATIC S7 Network
(MPI/DP)
Connecting an S7 Programmable Controller via an MPI/DP Interface
You can use the potential-separated*) MPI/DP interface to connect the SIMATIC
Field PG to a SIMATIC S7 programmable controller or to a PROFIBUS network.
The MPI patch cord (5m) for connecting to SIMATIC S7-CPUs (Order no.:
6ES7901-0BF00-0AA0) is included in the consignment. The data transfer rate is
limited to 187.5 Kbit/s when using this patch cord. For baud rates > 1.5 Mbit/s you
must use a PROFIBUS cable for 12 Mbit/s (Order no. 6ES7901-4BD00-0XA0).
6ES7901-0BF00-0AA0
(5–m length)
For environments free
of interference:
Bus connector
6ES7972-0BB10-0XA0
or
6ES7972-0BB20-0XA0
MPI/DP interface
Fig. 3-12
Connection Using the MPI/DP Interface
Proceed as follows when connecting to a SIMATIC S7 programmable logic
controller:
1. Switch off your device.
2. Open the interface cover on the left-hand side panel of the device.
3. Connect the cable to the MPI/DP interface.
Caution
Before plugging in the cables, the static charge on your body, the unit, and the
cables must be equalized. You can do this by briefly touching the metal mounting
plate for the interfaces on the rear panel.
*) Electrical isolation in the safety extra-low voltage circuit (SELV circuit).
Summary of Contents for Simatic Field PG
Page 8: ...Preface viii SIMATIC Field PG Manual A5E00075760 04 ...
Page 12: ...Contents xii SIMATIC Field PG Manual A5E00075760 04 ...
Page 18: ...Important Notes 1 6 SIMATIC Field PG Manual A5E00075760 04 ...
Page 90: ...Error Diagnostics 6 2 SIMATIC Field PG Manual A5E00075760 04 ...
Page 124: ...Technical Specifications B 6 SIMATIC Field PG Manual A5E00075760 04 ...