ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
153
Commissioning
6
6.1
PROFIBUS DP
6.1.1
Commissioning ET 200pro
Introduction
You commission the automation system according to the relevant plant configuration. The
procedure outlined below only describes the commissioning of ET 200pro connected to a DP
master.
Requirements
Table 6- 1
Requirements for commissioning
Actions
Reference
ET 200pro is mounted
Chapter
Mounting
The PROFIBUS DP address is set on ET 200pro
Chapter
Mounting
ET 200pro is wired
Chapter
Wiring
ET 200pro is configured
Chapter
Configuring
The supply voltage to the DP master is ON
DP master manual
The DP master is set to RUN mode
DP master manual
Commissioning ET 200pro
1.
Switch on the electronic / encoder supply 1L+ for ET 200pro.
2.
Switch on the load voltage supply/ies 2L+.
Note
Changes to the backplane bus
Always switch off/on power to the electronic/encoder supply 1L+ before you modify the
backplane bus configuration (number of modules, PROFIBUS address, removal of the
terminating module).
See also
Configuring in STEP 7 (Page 139)
Configuring by Means of GSD File (Page 140)