Communication with the redundant system S7-1500R/H
13.6 Open User Communication with the redundant system S7-1500R/H
Communication
336
Function Manual, 11/2019, A5E03735815-AH
13.6
Open User Communication with the redundant system S7-1500R/H
The following table shows which protocols of the Open User Communication you can use for
the S7-1500R/H redundant system and the matching system data types and instructions.
Table 13- 1 Protocols, system data types and usable instructions for Open User Communication with
the redundant system S7-1500R/H
Protocol
System data type
Instructions
TCP
•
TCON_QDN
•
TCON_IP_v4
Establish connection and send/receive data via:
•
TSEND_C/TRCV_C or
•
TCON, TSEND/TRCV or
•
TCON, TUSEND/TURCV
(connection can be terminated via TDISCON)
ISO-on-TCP
•
TCON_IP_RFC
UDP
•
TCON_IP_v4
•
TADDR_Param
•
TADDR_SEND_QDN
•
TADDR_RCV_IP
Establish connection and send/receive data via:
•
TSEND_C/TRCV_C
•
TUSEND/TURCV/TRCV
(connection can be terminated via TDISCON)
Modbus TCP
•
TCON_IP_v4
•
TCON_QDN
•
MB_CLIENT
•
MB_SERVER
13.6.1
Setting up the connection of the Open User Communication with the redundant
S7-1500R/H system
Introduction
The S7-1500R/H redundant system can communicate with other devices via Open User
Communication.
You set up the connections in the user program, e.g. via the "TSEND_C" instruction. The
S7-1500R/H redundant system does not support configured connections.
You can either set up the connections either via the device IP addresses or via the system IP
addresses of the PROFINET interfaces.
Open User Communication via a system IP address of the redundant system S7 1500R/H
If you set up the connection via a system IP address, then communication always takes
place via the primary CPU.
Recommendation: Always use a system IP address for Open User Communication.