ET 200SP Communication module CM 1xDALI (6ES7137-6CA00-0BU0)
Manual, 06/2019, A5E46959434-AA
21
Parameters
4
4.1
Parameter assignment
Introduction
You configure and assign the parameters of the communication module with STEP 7 V15.1
or later versions.
In the CM 1xDALI project, you assign the parameters in the device view of STEP 7 and in
the properties tab of the communication module DALI.
4.2
CM 1xDALI Module Parameters
Module Parameters
Each CM 1xDALI has the following DALI parameters in Module Parameters. According to
your request, you can configure any of these parameters.
The following table shows the module parameters for the CM 1xDALI.
Table 4- 1
Module Parameters
Module Parameters
Description
Value range
Default
value
Configura-
tion in
RUN
Basic parameter
Enable integrated
DALI bus power sup-
ply
Enable or disable the DALI bus power supply.
•
Enable: Use the integrated DALI bus power in the CM
1xDALI.
•
Disable: Do not use the integrated DALI bus power in
the CM 1xDALI.
•
Enable
•
Disable
Enable Yes
Enable DALI Applica-
tion Controller
Enable or disable DALI Application Controller.
•
Enable: The CM 1xDALI can send any forward frame
or receive any backward frame to the DALI bus.
•
Disable: The CM 1xDALI cannot send any forward
frame or receive any backward frame to the DALI bus.
•
Enable
•
Disable
Enable Yes