Fail-Safe Modules
7.2 PM-E F pm DC24V PROFIsafe Power Module
ET 200S Distributed I/O System - Fail-Safe Modules
68
Installation and Operating Manual, 08/2008, A5E00103686-07
WARNING
The SF LED and the status displays of the inputs/outputs are not designed for safety-
related functions and may therefore not be evaluated for safety-related activities.
Terminal Assignment
The following figure and the following table show the terminal assignment of the PM-
E F pm DC 24V PROFIsafe for the supported terminal modules TM-P30S44-A0 or TM-
P30C44-A0.
'&9'&9
00
$8;$8;
'2'2
33
'2'2
00
'2'2
33
$8;
'2'2
00
$
$
$
$
,QIHHG
,QIHHG
,QIHHG
Figure 7-4
Terminal assignment TM-P30S44-A0 or TM-P30C44-A0 for PM-E F pm DC 24V
PROFIsafe
Table 7- 2
Terminal assignment of the TM-P30S44-A0 or TM-P30C44-A0
Terminal
Designation
2
24 VDC
24 VDC rated load voltage for:
•
Inserted power module
•
Corresponding potential group
•
DO 0 and DO 1
•
Voltage buses P1 and P2
3
M
Ground
A
4
AUX 1
Any terminal for PE or voltage bus up to the maximum rated load voltage of the
module
6
24 VDC
24 VDC rated load voltage for:
•
Inserted power module
•
Corresponding potential group
•
DO 0 and DO 1
•
Voltage buses P1 and P2
7
M
Ground