ET 200pro FC
Operating Instructions, 07/2016, A5E01100763B AC
155
Technical data
10
10.1
Technical data
Technical data
General technical data and information about the mechanical and climatic environmental
condition of the ET 200pro system is provided in the "SIMATIC ET 200pro Distributed I/O
System" manual.
Note
Deviating from this general technical data, for the ET 200pro FC-2 inverter, the following
applies:
Drop test (in original package) ≤ 0.35 m.
Table 10- 1 Technical data
Date
Unit
Value
Rated input voltage
V
AC 400
Permissible voltage range min.
V
AC 380
Permissible voltage range max.
V
AC 480
Rated output current
@ 45 °C
A
3.9
@ 55 °C
A
3.5
Maximum output current (3 s)
A
2 x rated output current
Rated input current 3AC
A
3.7
Integrated device fuse
A
16, medium time-lag
Rated power @ 55 °C
kW
1.10
Power with overload (150% for 60 s every 300 s)
kW
1.65
Power with overload (200% for 3 s every 300 s)
kW
2.20
Power without overload capability
kW
1.20
Integrated brake control
V
DC 200
Pulse frequency (factory setting)
kHz
4
Installation altitude above sea level
m
2000
Efficiency η
%
95 … 97
Power factor
---
0.9
Summary of Contents for Simatic ET 200pro FC
Page 1: ......
Page 2: ......
Page 12: ...Table of contents ET 200pro FC 12 Operating Instructions 07 2016 A5E01100763B AC ...
Page 180: ...Appendix A 3 Standards ET 200pro FC 180 Operating Instructions 07 2016 A5E01100763B AC ...
Page 192: ...Glossary ET 200pro FC 192 Operating Instructions 07 2016 A5E01100763B AC ...
Page 195: ......
Page 196: ......