Installation
4.11 Mounting ET 200pro FC-2 fail-safe devices
SIMATIC ET 200pro FC-2 converter
56
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Power transmission jumper
The power jumper connector is used to loop-through the main power from one frequency
converter/motor starter to the next converter/motor starter.
The table below shows the assignment of the contacts:
Table 4- 4
Power jumper connector
Pin
Socket
Assignment
1
1
Phase L1
2
2
Phase L2
3
3
Phase L3
4
4
Not assigned
PE
4.11
Mounting ET 200pro FC-2 fail-safe devices
In principle, failsafe applications are configured the same as standard applications.
Differences in this regard include:
●
A module must be inserted to the left of the frequency converter, via which the inverter
safety functions are controlled:
–
Repair switch module F-RSM
–
F-Switch
●
Only the following modules may be inserted between F-RSM or F-Switch and the inverter:
–
400V switch off module
–
all direct or reversing starters
Procedure
Mount them one after the other:
1.
Module rack
2.
Interface module
3.
Bus module for F-RSM or F-Switch
4.
Bus module for frequency converters
5.
Termination module
6.
Connection module for the interface module