Backing up data and series commissioning
8.6 Know-how protection
SIMATIC ET 200pro FC-2 converter
204
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
8.6.2
Activating and deactivating know-how protection
Activating know-how protection
Preconditions
●
The inverter has now been commissioned.
●
You have generated the exception list for know-how protection.
●
To guarantee know-how protection, you must ensure that the project does not remain at
the end user as a file.
Procedure with STARTER
1.
Go online with STARTER.
If you have generated a project offline on your computer, you must load the project into
the inverter and go online.
2.
Select the required inverter in the project.
3.
In the shortcut menu, select "Know-how protection drive unit/activating ....".
4.
The "Without copy protection" option is active by default. If an appropriate memory card is
inserted in the Control Unit, you can select one of two copy protection options:
–
With basic copy protection (permanently linked to the memory card)
–
With extended copy protection (permanently linked to the memory card and Control
Unit)
Select the required copy protection option.
5.
If, in spite of active know-how protection, you wish to permit diagnostic functions, activate
option "Allow diagnostic functions (trace and measuring functions)".
6.
Click on "Define"