Advanced commissioning
7.20 Switchover between different settings
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
189
●
Get_Measurement_Values
The command returns the requested measured value using the measured value ID
●
Get_Measurement_Values_with_object_number
The command returns the requested measured values using the measured value ID and
the object number. The object number corresponds to the drive object ID.
Error values
Table 7- 35 Error values in the parameter response
Error
value 1
Meaning
001 hex Invalid Service_Request_ID
03 hex
Invalid Modifier
04 hex
Invalid Data_Structure_Identifier_RQ
06 hex
No PE energy-saving mode supported
07 hex
Response too long
08 hex
Invalid Block Header
50 hex
No suitable energy-saving mode available
51 hex
Time is not supported
52 hex
Impermissible PE_Mode_ID
53 hex
No switch to energy saving mode because of state operate
54 hex
service or function temporarily not available
7.20
Switchover between different settings
There are applications that require different inverter settings.
Example:
You connect different motors to one inverter. Depending on the particular motor, the inverter
must operate with the associated motor data and the appropriate ramp-function generator.
Drive data sets (DDS)
Your can set several inverter functions differently and then switch over between the different
settings.
The associated parameters are indexed (index 0, 1, 2, or 3). Using control commands select
one of the four indexes and therefore one of the four saved settings.
The settings in the inverter with the same index are called the drive data set.