Configuration Options
ET 200iS Distributed I/O Station
A5E00087831-02
4-5
4.4
Configuration Options in Zones
General Rules
Regardless of the configuration of the ET 200iS in zone 1, zone 2 or in the safe
area, the following rules apply:
If the inputs and outputs to the actuators are intrinsically safe, then
PROFIBUS-DP must also be intrinsically safe (Ex i):
1. Fieldbus isolating transformer required (for example, from R. STAHL
Schaltgeräte GmbH; Refer to the order numbers)
2. Marking of PROFIBUS-DP as Ex i (not only in zone 1!)
3. Marking of the cables/wires to the actuators and sensors as Ex i (for example,
using the color light blue).
Warning
All devices you connect to PROFIBUS-DP Ex i (on the Ex side of the fieldbus
isolating transformer) must be intrinsically safe.
Connecting voltage measurement devices, oscillographs, and bus testers to
PROFIBUS-DP Ex i is not permitted.
Rules for Configuring the ET 200iS in Zone 1:
If you use the ET 200iS in zone 1, you must adhere to the following rules:
1. The ET 200iS must be installed in an enclosure with type of protection EEx e
(increased safety). For information on ordering such enclosures, contact your
Siemens representative
2. PROFIBUS-DP must be isolated using a fieldbus isolating transformer. The
fieldbus isolating transformer (for example from R. STAHL Schaltgeräte GmbH;
refer to the section Order Numbers) guarantees degree of protection EEx i for
PROFIBUS-DP in hazardous areas (zone 1).
The fieldbus isolating transformer must be installed in the safe area. See
Appendix Order Numbers.
3. Normal PROFIBUS-DP bus cables can be used in zone 1. See appendix Order
Numbers. You must, however, mark these as "EEx i bus cable" (for example
with a blue band/blue shrink-on sleeve at the ends or mark the cable with a blue
color).
Summary of Contents for SIMATIC ET 200iS
Page 20: ...Preface ET 200iS Distributed I O Station 1 6 A5E00087831 02 ...
Page 34: ...Product Overview ET 200iS Distributed I O Station 2 14 A5E00087831 02 ...
Page 84: ...Installation ET 200iS Distributed I O Station 5 18 A5E00087831 02 ...
Page 168: ...Maintenance ET 200iS Distributed I O Station 8 6 A5E00087831 02 ...
Page 184: ...Terminal Modules ET 200iS Distributed I O Station 10 8 A5E00087831 02 ...
Page 188: ...Power Supply Module ET 200iS Distributed I O Station 11 4 A5E00087831 02 ...
Page 320: ...Dimension Drawings ET 200iS Distributed I O Station 17 4 A5E00087831 02 ...
Page 330: ......
Page 332: ...Certifications ET 200iS Distributed I O Station 20 2 A5E00087831 02 ...
Page 333: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 3 ...
Page 334: ...Certifications ET 200iS Distributed I O Station 20 4 A5E00087831 02 ...
Page 336: ...Certifications ET 200iS Distributed I O Station 20 6 A5E00087831 02 ...
Page 337: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 7 20 1 3 Power supply PS ...
Page 338: ...Certifications ET 200iS Distributed I O Station 20 8 A5E00087831 02 ...
Page 339: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 9 20 1 4 4DI NAMUR ...
Page 340: ...Certifications ET 200iS Distributed I O Station 20 10 A5E00087831 02 ...
Page 341: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 11 ...
Page 342: ...Certifications ET 200iS Distributed I O Station 20 12 A5E00087831 02 20 1 5 2DO DC25V 25mA ...
Page 343: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 13 ...
Page 347: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 17 ...
Page 348: ...Certifications ET 200iS Distributed I O Station 20 18 A5E00087831 02 20 1 8 2AI RTD ...
Page 349: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 19 ...
Page 350: ...Certifications ET 200iS Distributed I O Station 20 20 A5E00087831 02 20 1 9 2AI TC ...
Page 351: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 21 ...
Page 352: ...Certifications ET 200iS Distributed I O Station 20 22 A5E00087831 02 20 1 10 2AO I 2AO I HART ...
Page 353: ...Certifications ET 200iS Distributed I O Station A5E00087831 02 20 23 ...
Page 366: ...Marking ET 200iS Distributed I O Station 21 8 A5E00087831 02 ...
Page 416: ...26 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 417: ...27 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 418: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 01 ...
Page 419: ...28 Produktinformation RS 485 IS Koppler 6ES7 972 0AC80 0XA0 A5E00207082 01 ...
Page 420: ...28 Product Information RS 485 IS Coupler 6ES7 972 0AC80 0XA0 A5E00207628 02 ...