Technical data
6-2
ET 200eco Distributed I/O Station
A5E00158716-02
6.1
ECOFAST terminal block (6ES7 194-3AA00-0AA0)
Properties
Characteristics of the ECOFAST terminal block:
•
Can be plugged in and screwed on to any I/O module.
•
Connection to power supplies and PROFIBUS DP via ECOFAST connector (at
socket X01, supply lines).
•
Looping the power bus and PROFIBUS DP to the next PROFIBUS node via
additional ECOFAST connector (at socket X02, loop–through).
•
Internally interconnected supply line socket X01 and loop–through socket X02
(T functionality).
•
Adjustable PROFIBUS address (1 to 99) via configuration plug.
Note
The ECOFAST terminal block may only be operated with the I/O modules
6ES7 14*-3B*00-0XA0.
Pin assignment of the ECOFAST sockets
The table below shows the pin assignment of the two ECOFAST sockets for the
connection to the power supplies and PROFIBUS DP.
Table 6-1
Pin-out of the sockets X01 and X02
Pin
Assignment of the
infeed socket X01
Assignment of the
through–loop socket
X02
View of the socket (Front
view of the terminal
blocks)
A
PROFIBUS DP Signal A
B
PROFIBUS DP Signal B
A
B
1
Electronic/sensor power supply (1L+)
A
B
2
Ground potential, sensor power supply (1M)
1
2
3
4
3
Ground potential, load voltage supply (2M)
4
Load voltage supply (2L+)
Summary of Contents for SIMATIC ET 200eco
Page 8: ...Preface viii ET 200eco Distributed I O Station A5E00158716 02 ...
Page 18: ...Product overview 1 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 70: ...Commissioning and diagnostics 4 16 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 116: ...I O address area C 6 ET 200eco Distributed I O Station A5E00158716 02 ...
Page 124: ...Index Index 4 ET 200eco Distributed I O Station A5E00158716 02 ...