ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
200
IO-Link Master
11
11.1
IO-Link Master (6ES7148-6JA00-0AB0)
Article number
6ES7148-6JA00-0AB0
Properties
The IO-Link Master 4 IO‑L + 8 DI + 4 DO DC 24V/1,3A 8×M12 has the following technical
specifications:
• IO-Link Master according to IO-Link specification V1.0
• Dimensions 60 x 175 mm
• Double assignment of the sockets
• 4 IO-Link ports (Port Class A)
• IO-Link ports can be used optionally as:
– 4 IO‑Link devices as 3‑conductor connection
– 4 standard actuators/encoders (SIO mode)
• 8 digital inputs and 4 digital outputs
• Digital inputs
– Rated input voltage DC 24 V
– Suitable for switches and proximity switches
– Diagnostics
"Missing 2L+" for the I/O device
"Short-circuit to M at sensor supply", per channel group
"Wire break", per channel
– Channels 4 to 7 are diagnostics-capable, Channels 0 to 3 do not have diagnostics.
• Digital outputs
– Rated load voltage DC 24 V
– Output current: 1.3 A per output
– Suitable for solenoid valves, DC contactors, and indicator lights
– Diagnostics
"Missing 2L+" for the I/O device
"Wire break at outputs" per channel
"Short-circuit to M at outputs" per channel
– Parameterizable response to CPU/Master STOP
• Data transfer rates COM1 (4.8 kBaud), COM2 (38.4 kBaud)