3-6
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
3.3
Digital Output Module ET 200C; DO 8
DC 24V/2A
(6ES7 142-0BF10-0XB0)
The digital output module ET 200C; DO 8
DC 24V/2A has the following
characteristics:
Degree of protection IP 66/IP 67 (see Installation rules, Section 4.1)
Output current per channel: 2 A
Choice of nine different baud rates:
9.6, 19.2; 93.75; 187.5; 500; 1500; 3000; 6000 and 12000 kbaud
The baud rates 3000, 6000 and 12000 kbaud can only be used if the
module is operated with the IM 308-C (see Section 1.2).
Channel-by-channel diagnostics of the outputs for wire break and
short-circuit/overload and load voltage of the outputs (can be switched off
with COM ET 200, see Section 5.1.4).
The diagnostics can be output via the IM 308-B master interface module.
In addition, each diagnostic message causes the LED ”DIA” or the
respective individual diagnostics LED to light up.
LEDs for
–
RUN
–
BF (bus fault)
–
DIA (diagnostics of the outputs)
–
U
L
(load voltage supply of the outputs)
–
Status of the outputs or individual diagnostics
Attachment of the module without opening the cover (drill-hole template
at the back of the manual)
Characteristics
ET 200C Components
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...